An excessively long cable on a wired differential pressure sensor can indeed affect measurement results, but this does not mean that extending the cable will inevitably cause a significant loss of accuracy. The actual impact depends on the sensor output type, supply voltage, cable specification, on-site electromagnetic environment, grounding method, and input characteristics of the downstream acquisition equipment.
For 4-20mA two-wire differential pressure transmitters commonly used in industrial applications, appropriately extending the cable will generally not directly change full-scale accuracy, as current signals offer good long-distance transmission capability. However, if the line voltage drop is excessive, the power supply margin is insufficient, or strong interference is present, the output current may not stably reflect the actual differential pressure value.
For voltage-output products such as 0-5V, 0-10V, and 1-5V, cable length and conductor resistance have a more pronounced impact. As the distance increases, line voltage drop, signal attenuation, and common-mode interference all increase. This is especially significant in low-range differential pressure measurement, where even minor voltage fluctuations may result in substantial reading errors.
Therefore, determining whether a cable is “too long” cannot be based solely on the number of meters; it should be assessed in conjunction with loop calculations and operating conditions. With proper selection of shielded cables, sufficient power supply margin, and standardized cable routing, wired differential pressure sensors can still maintain good stability over transmission distances of dozens or even hundreds of meters.
The longer the cable, the greater the conductor resistance. A two-wire 4-20mA differential pressure transmitter draws power through the line while outputting its signal through the same loop, and line resistance consumes part of the supply voltage. When the actual operating voltage at the sensor falls below the allowable minimum, output limiting, display fluctuations, or failure to reach 20mA at full scale may occur.
For example, in a 24VDC power supply system, if the transmitter's minimum operating voltage is 10.5V and the controller input resistance is 250Ω, the input consumes approximately 5V at the 20mA full-scale value. Only the remaining voltage can compensate for cable voltage drop. In this case, the allowable line voltage drop is approximately 8.5V, rather than allowing unlimited cable extension.
Taking a 0.75mm² copper-core cable as an example, the resistance of a single core is approximately 24Ω/km. If the transmission distance is 500m, the round-trip loop length is approximately 1000m, and the loop resistance is approximately 24Ω. At 20mA, the cable voltage drop is approximately 0.48V, which is usually still within a controllable range.
If conductors with an excessively small cross-sectional area are used, or if the transmission distance exceeds 1km, voltage drop must be carefully calculated. For low-supply-voltage systems, products with digital display heads, or loops with high load requirements, a more sufficient power supply margin should be reserved.
Strong electromagnetic interference may occur near variable frequency drives, motors, welding machines, high-power contactors, and high-voltage cables. Long cables effectively increase the signal reception length. If shielding, grounding, and cable routing are not properly implemented, interference is more likely to couple into the measurement loop.
On site, interference commonly manifests as periodic fluctuations in displayed differential pressure values, sudden reading changes when equipment starts or stops, PLC sampling value jitter, or short-term zero-point instability. For low differential pressure applications with ranges of only 0-1kPa or 0-5kPa, such effects are particularly significant.
4-20mA signals generally offer better interference immunity than voltage signals because the receiving end identifies loop current rather than absolute voltage. However, current output is not completely immune to interference. Measurement noise may still be introduced, particularly when the shield layer is left floating, grounded at multiple points, or when power supply negative terminals are interconnected.
It is recommended that signal cables and power cables be routed separately, with a parallel spacing of at least 300mm. Where this cannot be avoided, they should cross vertically whenever possible. In high-interference environments, twisted-pair shielded cable should be prioritized, and the shielding layer should be reliably grounded at one end in accordance with system requirements.
The signal type of a differential pressure sensor determines its sensitivity to cable length. During the engineering selection stage, the control system interface and transmission distance should be confirmed first, followed by selection of a 4-20mA, voltage output, or RS485 communication solution.
Generally, 4-20mA is suitable for most industrial long-distance measurement applications; voltage signals are more suitable for internal equipment connections or short-distance connections; RS485 digital communication is suitable for multi-point networking, but terminal resistance, communication protocol, and wiring topology requirements must be met.
For cleanroom pressure differential, air duct differential pressure, filter clogging monitoring, and similar applications, 4-20mA output should be prioritized if the sensor is more than 50m from the control cabinet. For operating conditions with strong interference, such as chemical energy and metallurgy and building materials applications, isolated power supplies and signal isolator configurations should also be evaluated.
The table below may serve as a reference for standard engineering selection. The actual maximum distance should still be determined based on the product manual, power supply conditions, and on-site test results.
A larger cable cross-sectional area is not always better; it should be selected comprehensively based on distance, loop current, ambient temperature, and installation method. For conventional short-distance instrument wiring, 0.5mm² or 0.75mm² cables may be used; when the distance is longer or the on-site temperature is higher, this can be increased to 1.0mm² or 1.5mm².
For 4-20mA loops, a preliminary calculation can be made using “allowable line resistance = allowable voltage drop ÷ 0.02A.” For example, when the allowable line voltage drop is 6V, the allowable total loop resistance is approximately 300Ω. The usable distance can then be estimated based on the cable resistance per unit length.
Oxidized field wiring terminals, loose crimping, and water ingress into intermediate joints can also increase contact resistance. Even if the main cable is correctly selected, these details may still cause intermittent faults. Therefore, unnecessary intermediate joints should be minimized, and moisture-proof sealing should be properly implemented.
Differential pressure measurement systems must also distinguish between an “excessively long cable” and an “excessively long impulse line.” An excessively long cable mainly affects electrical signals and power supply, while an excessively long impulse line may cause medium condensation, leakage, delayed response, and static pressure differential errors. The two issues need to be addressed separately.
For new projects, sensor installation locations, control cabinet locations, supply voltage, and cable routing should be incorporated into the design in advance. For differential pressure measurement points with transmission distances exceeding 100m, it is recommended to complete loop voltage drop calculations during the drawing stage rather than making adjustments only after output abnormalities occur on site.
For applications with high accuracy requirements, in addition to focusing on transmission cables, it is also necessary to confirm whether the sensor range is appropriate. Keeping the measured differential pressure within 30% to 80% of the range over the long term is generally more conducive to obtaining stable and distinguishable measurement results. Selecting an excessively large range will amplify the effect of zero-point fluctuations on actual readings.
Xi'an Shenghongchuang Instrumentation Co., Ltd. can provide multiple output configurations, including 4-20mA and RS485, based on differential pressure range, medium characteristics, installation environment, transmission distance, and control system interface, together with cable selection, power supply calculations, and interference-resistance solution recommendations.
If your differential pressure sensor has issues such as long-distance transmission, signal fluctuations, inaccurate display, or insufficient full-scale output, it is recommended to compile the on-site supply voltage, cable length, conductor size, output type, and load parameters, and contact professional technical personnel for loop calculations and targeted selection to ensure stable operation of the measurement system as soon as possible.