How to Handle Unstable On-Site Readings of a Digital Differential Pressure Sensor
Added to Favorites:125

How to Handle Unstable On-Site Readings of Digital Differential Pressure Sensors

Digital differential pressure sensors are used to monitor the pressure difference between two points and are commonly used in applications such as air duct static pressure, filter blockage, cleanroom pressure differential, liquid level differential pressure, boiler forced-air supply, and industrial pipeline control. When on-site values fluctuate, displays rise and fall irregularly, zero drift occurs, or output signals fluctuate, the sensor should not be directly judged as damaged. The process conditions, installation method, power supply quality, pressure-sensing lines, and signal transmission conditions should be checked item by item.

Under normal conditions, when process pressure is relatively stable, display fluctuations of a digital differential pressure sensor should remain within the range permitted by its measuring range and resolution. For example, for a product with a range of 0–1 kPa, a slight display variation of 1–3 Pa may be normal; if readings continuously fluctuate by more than 2%–5% of full scale or repeatedly span a large range within a short period, sources of interference or abnormal measurement conditions should be investigated.

On-site troubleshooting should follow the principle of “process first, installation second; external factors first, internal factors second.” First confirm whether the actual differential pressure is changing, then inspect the conditions around the sensor to avoid pipeline leakage, loss of zero point, or shutdown risks caused by blind disassembly. Where high-temperature, high-pressure, or corrosive media are involved, handling should be performed by qualified personnel in accordance with on-site safety procedures.

I. First Determine Whether It Is Actual Differential Pressure Fluctuation or Abnormal Instrument Display

Check Process Operating Conditions

Changes in fan frequency, frequent valve operation, pump start-stop cycles, uneven dust accumulation on filters, and pulsating flow in pipelines can all cause dynamic changes in the differential pressure itself. Particularly in variable-frequency fan systems, each air volume adjustment causes a static pressure change, and the fluctuations reflected by the digital differential pressure sensor may not necessarily indicate a fault.

When the sensor display is abnormal, simultaneously check the variable-frequency drive frequency, valve opening, control system trend curves, and readings of mechanical gauges at the same location. If multiple measurement points show consistent trends, this indicates that process-side fluctuations do exist; if only one digital differential pressure sensor fluctuates, focus on inspecting the pressure tapping, wiring, and instrument parameters.

For relatively stable operating conditions such as cleanrooms and filter monitoring, temporarily keep the fan frequency and damper opening unchanged and observe continuously for 3–5 minutes. If the environment is stable but the readings still fluctuate irregularly, and the fluctuation amplitude exceeds half of the set alarm threshold, proceed to the next troubleshooting step.

Use the Isolation Method for Preliminary Fault Localization

Provided that safety is ensured, connect both the high-pressure and low-pressure sides to the same stable pressure environment, or perform a zero-pressure check according to the product instructions. The theoretical differential pressure should then be close to zero. If the display continues to fluctuate, the issue is more likely related to the power supply, signal interference, internal components, or parameter settings.

If the display remains stable after both sides are connected to the same pressure but fluctuates again after restoring the pressure connections, inspect the pressure tap locations, impulse line sealing, condensate, and blockage conditions. For gas differential pressure measurement, pressure pulsation can be directly caused by local turbulence when pressure tapping points are too close to fans, elbows, or valves.

After the isolation test, restore the original connections and reconfirm the direction of the high-pressure and low-pressure sides. Reversed high- and low-pressure connections usually result in negative values or trends opposite to actual operating conditions. Although this may not necessarily cause fluctuations, it can interfere with subsequent fault diagnosis.

Field SymptomsPriority Troubleshooting DirectionRecommended Action
Readings change in sync with fan or valve operationActual process fluctuationsVerify the control logic and set damping if necessary
The display changes randomly, and the output signal is also unstablePower supply, grounding, and signal interferenceCheck the 24VDC power supply and shield grounding
The display fluctuates, but the analog output remains stableDisplay resolution or display parametersAdjust decimal places, filtering, and display refresh parameters
A significant deviation remains after shutdownZero drift, blockage, or accumulated liquidPerform zero calibration after cleaning the piping

II. Check the Installation Location and Pressure-Sensing Lines

Avoid Installation Locations with Strong Vibration and High Pulsation

Digital differential pressure sensors should be installed in locations that are easy to observe, have low vibration, and offer suitable temperature and humidity conditions. If directly mounted on fan housings, near compressors, on stamping equipment, or on high-frequency vibrating brackets, long-term mechanical vibration may loosen wiring terminals and may also subject internal sensing elements to additional stress.

Pressure tapping points for gas differential pressure measurement should avoid strong turbulence zones downstream of fan outlets, sharp bends, tees, and control valves. A relatively stable location on a straight pipe section can generally be selected, with high- and low-pressure tapping points positioned within appropriate measurement areas. For air duct static pressure measurement, the area around pressure tapping points should be kept clean and free from insulation wool, sealant, or dust accumulation.

For liquid or steam differential pressure measurement, the length, routing, and medium condition of the impulse lines on both sides should be as consistent as possible. Excessive elevation differences, obvious temperature differences, or condensate retained on one side can introduce additional static pressure, causing unstable display values or continuous offsets.

Eliminate Air Leakage, Blockage, and Liquid Accumulation

Aging hoses, loose clamps, and fittings that are not fully inserted are common issues in low-range differential pressure measurement. For products with ranges of 0–250 Pa and 0–500 Pa, even minor air leakage may cause slow value drift or intermittent fluctuations. During inspection, pay particular attention to fittings, tees, valve manifolds, and bent sections of impulse lines.

Water, oil contamination, dust, or crystallized material accumulated inside impulse lines can delay pressure transmission, resulting in lagging readings, sudden recovery, or continuous oscillation. Gas measurement lines should avoid low points where liquid can accumulate; liquid measurement should avoid trapped air bubbles; and steam measurement should ensure substantially consistent condensation conditions on both sides.

After cleaning the pipeline, do not judge the result based on a single reading immediately. Observe for a period after operating conditions have stabilized. If the zero point changes noticeably before and after cleaning, perform zero calibration again and record the difference before and after calibration for subsequent maintenance tracking.

Key Points for Inspecting Pressure-Sensing Lines

Check whether impulse hoses are flattened, cracked, detached, or excessively bent; confirm that the high-pressure side is connected to the high-pressure tapping point and the low-pressure side to the low-pressure tapping point; and confirm that drain valves, equalizing valves, and shutoff valves are in the correct positions. After disassembly and reassembly, ensure all connections are secure to prevent abnormal differential pressure direction caused by incorrect connections.

For applications with high dust concentration or oil mist, establish a regular drainage and cleaning schedule. The actual interval may be determined according to the degree of on-site contamination, for example, inspection once per month, or once per week under harsh operating conditions, to prevent blockages from developing into measurement distortion.

If impulse lines need to be extended on site, they should not be lengthened blindly. Excessively long lines increase response lag and are more likely to cause condensation, liquid accumulation, and leakage points. Where remote installation is necessary, technical personnel should evaluate the pipe diameter, material, and routing method based on the medium, temperature, measuring range, and response requirements.

III. Investigate Power Supply Quality and Electromagnetic Interference

Confirm Power Supply Voltage and Wiring Reliability

Most industrial digital differential pressure sensors use a 24VDC power supply, and the actual supply voltage should comply with the requirements specified on the product nameplate and in the instruction manual. Insufficient power capacity, poor-quality switching power supplies, or multiple high-power loads sharing the same power supply may cause instantaneous voltage drops, resulting in display flickering, reading drift, or communication interruption.

Use a multimeter to measure the voltage at the sensor power terminals rather than measuring only the power output terminals in the control cabinet. Also observe whether the voltage fluctuates significantly during equipment startup, variable-frequency drive acceleration, or simultaneous solenoid valve operation. Wiring terminals should be securely tightened, and wire lugs and shielding layers must not short-circuit with adjacent terminals.

For products with 4–20mA output, also check whether the loop load is within the permitted range. Excessive loop resistance, incorrect PLC analog input module wiring, or loose connections in the loop may cause fluctuations in host system values. Even if the sensor’s local digital display is normal, signal loop issues cannot be ruled out.

Ensure Proper Shielding and Wiring Isolation

Sensor signal cables should use shielded cables whenever possible and should be routed separately from variable-frequency drive output cables, motor power cables, and contactor coil wires. Long-distance parallel routing can easily induce interference. Where conditions permit, maintain a spacing of at least 200mm; where crossing is unavoidable, cross at an angle close to 90 degrees.

The shielding layer should generally be reliably grounded at one end only, subject to the product instructions and the grounding scheme of the control system. Arbitrary grounding at both ends of the shielding layer may create a ground loop and instead introduce low-frequency interference. The relationship among sensor housing grounding, control cabinet protective grounding, and signal grounding should also be planned consistently.

If reading fluctuations occur precisely when a variable-frequency drive starts, a welding machine operates, or high-power equipment is activated, temporarily switch off the relevant interference source for verification. After interference is confirmed, measurement stability can be improved by adjusting cable routing, adding an isolated power supply, using a signal isolator, or optimizing the grounding method.

Inspection ItemRecommended assessmentPotential Risks
Sensor-side power supplyWithin the voltage range specified on the nameplate and stable during operationDisplay flickering, output drift, or communication disconnection
Signal cable routingKeep away from power cables and variable-frequency drive output cablesRandom fluctuations or periodic interference
Shield layer treatmentGround at one end or as specified according to system requirementsGround loop interference and superimposed noise
4~20mA loopCorrect polarity, load, and module measurement rangeAbnormal host system display or full-scale deviation

IV. Verify Parameter Settings, Calibration Status, and Maintenance Methods

Set Damping and Display Parameters Appropriately

Some intelligent digital differential pressure sensors include parameters such as damping time, digital filtering, display refresh rate, and alarm delay. If damping is set too low, the instrument responds rapidly to minor disturbances, making the display appear to fluctuate frequently; if damping is set too high, actual process changes may be masked and control response may be affected.

For ventilation and filtration monitoring applications with high stability requirements, damping can be set to 1–5 seconds based on actual fluctuations and the effect observed. For control systems that need to capture differential pressure changes quickly, both response speed and anti-fluctuation capability should be considered, avoiding excessively high settings merely to make the display “appear stable.”

Range selection also affects the perceived reading stability. When the actual operating differential pressure remains below 10% of full scale for a long time, minor disturbances appear more noticeable on the display. Select an appropriate range based on the commonly used differential pressure, the maximum possible differential pressure, and accuracy requirements to avoid an excessively large or small range.

Perform Standardized Zero Checks and Calibration

Before zero calibration, confirm that the high-pressure and low-pressure sides are under the same pressure conditions, and eliminate residual pressure, liquid accumulation, and blockages in the impulse lines. Zero adjustment without depressurization or before pressures on both sides are balanced will result in an incorrect measurement reference, making subsequent readings appear stable while producing a large overall deviation.

For systems with high accuracy requirements, it is recommended to use a standard pressure source or calibrated test equipment for multi-point verification, for example, checking indicated values and outputs near 25%, 50%, 75%, and 100% of the measuring range. If calibration results exceed the product’s permissible error, make adjustments according to the instruction manual or contact technical service personnel.

If the sensor has experienced overpressure, medium backflow, high-temperature exposure, lightning surges, or a long-term highly corrosive environment, the performance of the sensing element may be affected even if there is no obvious external damage. In such cases, repeated forced zero adjustment is not recommended. First confirm the product measuring range, pressure resistance, and medium compatibility.

It Is Recommended to Establish On-Site Maintenance Records

For each maintenance activity, record the date, equipment number, measuring range, on-site medium, fluctuation range, supply voltage, pipeline inspection results, and calibration data. Continuous records can help determine whether a fault is due to occasional interference, changes in process conditions, or gradual degradation of sensor performance.

For critical control points, it is recommended to compare readings from the local digital display, PLC acquisition value, and process reference gauge. When the deviation among the three exceeds the system’s permitted range, first confirm the measurement reference and wiring configuration before deciding whether to replace the instrument, thereby avoiding increased maintenance costs caused by misjudgment.

Xi'an Shenghongchuang Instrumentation Co., Ltd. can provide digital differential pressure sensor selection, parameter setting, calibration maintenance, and non-standard supporting services for operating conditions such as air pressure, filter differential pressure, liquid level differential pressure, and pipeline differential pressure. When on-site readings remain unstable, it is recommended to compile the product model, measuring range, power supply method, wiring photos, installation location, and fluctuation data, so that professional technical personnel can make a targeted assessment based on actual operating conditions.