Common Causes and On-Site Troubleshooting Methods for Output Drift in Electronic Differential Pressure Sensors
Added to Favorites:125

Common Causes of Output Drift in Electronic Differential Pressure Sensors and On-Site Troubleshooting Methods

Electronic differential pressure sensors are used to detect the pressure difference between two pressure ports and are commonly used in air flow monitoring, filter differential pressure monitoring, level measurement, flow calculation, and closed-vessel control. During operation, if actual operating conditions remain basically stable while the displayed value, 4-20mA output, or control system trend continues to shift slowly, output drift may be occurring.

Drift is not the same as instantaneous fluctuation. Instantaneous fluctuations are usually related to medium pulsation, equipment start-up and shutdown, or electromagnetic interference; drift is more often characterized by a gradual zero-point deviation, increased full-scale error, or inconsistency between the measured value and the historical baseline under the same operating conditions. For a differential pressure sensor with a range of 0-10kPa, if the deviation under stable conditions has exceeded 50Pa to 100Pa, an inspection should be carried out promptly.

During after-sales maintenance, first distinguish between “sensor body drift” and “system measurement loop error.” Impulse line blockage, liquid accumulation at pressure taps, unstable power supply, improper grounding, and abnormal PLC analog input channels can all cause phenomena similar to sensor drift. Troubleshooting from the outside inward and from easy to difficult can reduce disassembly and downtime.

I. First Confirm Whether the Drift Actually Exists

1. Compare Process Conditions and Historical Trends

First check the trends on the DCS, PLC, or recorder to determine whether the deviation is continuous or occurs only under specific operating conditions. If equipment load, valve opening, medium temperature, and flow rate show no significant changes while the differential pressure value changes in one direction over several hours or days, the measurement loop should be examined closely.

For filter differential pressure monitoring, gradual filter element clogging will naturally increase the differential pressure; for closed-vessel level measurement, level changes will cause differential pressure changes. On-site personnel should not determine a fault based solely on changes in readings, but should verify whether the theoretical direction of differential pressure change is reasonable in conjunction with the production process.

The current value may be compared with records from the initial commissioning of the equipment, after the last calibration, or from a backup instrument. If the long-term baseline under the same operating conditions is 2.00kPa and the current stable display is 2.35kPa, with no change in process conditions, then the 0.35kPa deviation has clear troubleshooting significance.

On-Site Data to Record During Preliminary Assessment

Record the sensor model, range, output signal, supply voltage, installation location, medium type, and ambient temperature. For 4-20mA products, also record the measured loop current and the value acquired by the control system to avoid making judgments based only on the host computer display.

Also record the actual connection method on the high-pressure and low-pressure sides. When the positive and negative pressure ports of a differential pressure sensor are reversed, some systems may compensate through software reversal; however, restoring wiring after maintenance can easily cause an incorrect zero direction or abnormal range mapping.

It is recommended to photograph the valve manifold, impulse lines, and terminal wiring conditions before inspection and mark the open/closed positions of each valve. At sites equipped with a three-valve manifold or five-valve manifold, incorrect operation of the equalizing valve, drain valve, or shut-off valve may directly introduce new measurement errors.

PhenomenonPriority Suspected CausesOn-Site Verification Methods
Reading slowly rises or falls in one directionLiquid accumulation or blockage in the impulse line, zero driftBalance the pressure on both sides and check the zero output
Readings fluctuate irregularlyPower supply fluctuations, electromagnetic interference, poor contactMeasure the power supply and loop current, and check shield grounding
Differential pressure remains consistently highLow-pressure side blockage, high-pressure side leakageCheck impulse line continuity and sealing condition on both sides

II. Common Causes of Output Drift

1. Abnormal Pressure-Tapping System and Installation Conditions

Liquid accumulation, gas accumulation, crystallization, scaling, or impurity deposits in impulse lines are among the most common sources of on-site error. If condensate is present in the impulse line for gaseous media, it will increase the static pressure on one side; if air bubbles accumulate in the impulse line for liquid media, they will also cause measurement deviation.

Excessive differences in impulse line length between the high-pressure and low-pressure sides, or inconsistent insulation conditions, can also result in different medium densities on the two sides when temperatures change. Especially in steam, hot oil, or high-temperature gas applications, day-to-night temperature differences may cause the zero point to shift slowly with ambient changes.

Loose mounting brackets, noticeable sensor inclination, or vibration from equipment may also affect the stress condition of internal sensing elements. Installation should generally follow product requirements, avoiding direct installation of transmitters on strongly vibrating pump bodies, fan housings, or pipelines subject to frequent impact.

Valve Manifold, Sealing, and Leakage Issues

Internal leakage in the valve manifold can prevent pressure on both sides from remaining stable. In particular, when the equalizing valve is not completely closed, the differential pressure signal may be continuously weakened. At some sites, the valve handle may be in the correct position, but valve plug wear or damage to the sealing surface can still result in gradual pressure crossover.

Slight leakage at fittings, flanges, compression fittings, or gaskets may not produce obvious medium leakage, but may cause pressure on one side to drop. For vacuum, low differential pressure, or gas measurement applications, even very small leaks may result in reading errors of tens of pascals.

During inspection, pressure holding at connection points may be observed while ensuring safety. If, after process pressure is isolated, the pressure at the sensor input continues to decrease within 5 minutes to 10 minutes, pipeline sealing and valve manifold issues should be addressed before instrument calibration.

2. Effects of Electrical Loops and Environmental Factors

Insufficient or fluctuating 24VDC power supply can affect the output stability of electronic differential pressure sensors. Voltage should be measured directly at the sensor power terminals rather than only at the control cabinet power supply terminals; when wiring is long, terminals are oxidized, or loop load is high, the voltage at the far end may be significantly lower than the rated value.

Long-distance parallel routing of 4-20mA signal cables with variable frequency drives, motor power cables, or high-frequency equipment wiring may introduce interference. Interference is usually manifested as output fluctuation, but when analog module filtering or control program calculations are involved, it may also appear as a slow shift in the trend.

Ambient temperatures beyond the product compensation range will increase temperature drift. Although conventional industrial products have a certain temperature compensation capability, zero-point stability may still be affected by summer sun exposure, winter low temperatures, poor control cabinet heat dissipation, or proximity to high-temperature equipment.

Sensor Aging and Overpressure Damage

Long-term exposure to high static pressure, high temperatures, corrosive media, or frequent pressure shocks can alter the performance of the sensing element and isolation diaphragm. Especially when the differential pressure range is small but the actual static pressure on both sides is high, it is necessary to confirm whether the product static pressure rating and overload capacity meet the operating requirements.

Sudden pressure application on one side, incorrect valve closing, or improper blowdown operations may cause instantaneous diaphragm impact. After damage, the sensor may not immediately lose output, but problems such as failure of the zero point to return, degraded linearity, or reduced repeatability may occur.

If the sensor still cannot meet accuracy requirements under a standard pressure source after completing checks of the impulse system, power supply, and signal loop, factory inspection should be considered. Xi'an Shenghongchuang Instrumentation Co., Ltd. can provide corresponding technical assessment and handling recommendations based on the range, medium, installation method, and fault records.

III. Step-by-Step On-Site Troubleshooting Procedure

1. Safety Preparation and Visual Inspection Before Shutdown

Before troubleshooting, comply with on-site safety management requirements and confirm medium hazards, pressure rating, and isolation measures. When high-temperature, high-pressure, flammable, toxic, or corrosive media are involved, operations must be performed after confirmation by process personnel. Do not directly remove impulse fittings or open drain ports.

First inspect the appearance of the housing, junction box, impulse lines, and valve manifold for corrosion, seepage, looseness, water accumulation, and mechanical damage. Check whether the cable entry device is sealed, whether the wiring compartment is damp, and whether terminals are oxidized, blackened, or inadequately crimped.

For products with a display screen, compare the local display with the control system value. If the local display is normal but the PLC display has a significant deviation, the issue is more likely in the signal cable, isolator, or analog input module; if both drift simultaneously, continue checking the pressure input and sensor body.

Equalization Check and Loop Verification

After confirming that valve manifold operation is correct and both sides have been safely isolated, use the equalizing valve to place the high-pressure and low-pressure sides of the sensor at the same pressure. In theory, the differential pressure should then be close to zero; for 4-20mA products with 4.00mA corresponding to zero, use a high-precision multimeter to measure the actual current.

If the output in the equalized state deviates from 4.00mA, for example, remaining stable at 4.18mA, first verify the range setting and zero elevation/suppression parameters. For an instrument with a range of 0-10kPa, 0.18mA corresponds to an output deviation of approximately 1.125% of span, and it is necessary to determine whether this exceeds the allowable on-site error.

Then connect a multimeter in series in the loop or use a process calibrator to read the current and compare it with the PLC acquisition value. If the sensor output is 12.00mA but the corresponding system display value is abnormal, check the isolation barrier, wiring terminals, analog module range, and software engineering unit settings.

Troubleshooting StepsNormal Reference ResultsCorrective Action Direction
Measure the supply voltageThe voltage at the sensor meets the nameplate requirementsCheck the power supply, line voltage drop, and terminal contact
Balance check on both sidesOutput is close to zero or the configured offset valueCheck the zero point, valve manifold cross-pressure, and diaphragm condition
Apply standard pressureConsistent linearity at 25%, 50%, 75%, and 100% pointsCalibrate the sensor or return it to the factory for inspection

2. Standard Pressure Calibration and Fault Localization

Use a standard pressure source with an accuracy class higher than that of the instrument under test for calibration. It is recommended to select at least five test points: 0%, 25%, 50%, 75%, and 100%. The accuracy of the standard instrument should generally be better than one-third of the allowable error of the sensor under test to ensure reliable assessment results.

During calibration, record data for both the upstroke and downstroke. If there is a large difference between the upstroke and downstroke at the same pressure point, this may indicate hysteresis, mechanical stress, or internal component abnormalities; if deviations at all points are basically consistent, the condition is more likely zero-point drift or a parameter setting deviation.

Before on-site calibration, confirm whether the product allows zero adjustment and full-scale adjustment, and whether a password or dedicated communication tool is required. For differential pressure transmitters with digital compensation and intelligent communication functions, it is not recommended to modify settings blindly without understanding zero elevation/suppression, damping, and range parameters.

IV. Calibration Recovery and Preventive Maintenance Recommendations

1. Reinstallation and Acceptance After Calibration

After completing zero-point and range calibration, perform verification again at no fewer than 3 test points, and confirm that error, repeatability, and hysteresis all meet usage requirements. For applications with high control requirements, it is recommended to retain complete calibration records to facilitate subsequent assessment of drift trends.

When restoring process pressure, follow standardized valve manifold operating procedures to avoid sudden pressurization on one side. Generally, first confirm the equalized state, then slowly open the corresponding shut-off valves so that the high-pressure and low-pressure sides are gradually brought into service according to process requirements, preventing pressure shock to the sensing element.

After the instrument is put into operation, observe it for 15 minutes to 30 minutes and restore automatic control only after confirming stable output. If the reading is normal immediately after commissioning but begins to shift again after operating for a period of time, refocus on liquid accumulation in impulse lines, uneven insulation, ambient temperature changes, and actual process pulsation.

Establish a Periodic Maintenance Mechanism

For clean, normal-temperature, and low-corrosion operating conditions, calibration can be scheduled in conjunction with annual equipment maintenance; for dusty, high-humidity, high-temperature, easily crystallizing, or corrosive media, inspection intervals should be shortened. Filter differential pressure systems, dust removal systems, and wastewater treatment systems typically require greater attention to pressure-tap blockage.

Maintenance should include checking pressure-tap accessibility, impulse line sealing, valve manifold condition, cable shielding and grounding, supply voltage, and zero-point stability. It is recommended to establish records for instruments of the same type and continuously document calibration deviations to identify the risk of progressively increasing drift in advance.

When repeated drift, over-range impacts, diaphragm corrosion, or failure to pass standard pressure calibration occurs on site, do not continue operating based on temporary correction values. Please organize the product nameplate information, range, medium parameters, wiring method, and fault records, and contact the technical service personnel of Xi'an Shenghongchuang Instrumentation Co., Ltd. to obtain inspection, selection, or non-standard customization recommendations tailored to the operating conditions.