When sourcing a pressure transmitter with low measurement error, checking only the accuracy class may not be enough. The same accuracy percentage combined with different ranges can result in pressure errors that differ severalfold; when the same instrument is used in the lower part of its range, the error relative to the reading may also increase significantly. When selecting a model, check the accuracy definition, calibrated range, and operating conditions together.
Specifications such as “Class 0.1,” “Class 0.25,” or “Class 0.5” are commonly used to describe an instrument’s accuracy, but these figures should not be compared in isolation when purchasing. Ask the supplier to specify whether the error is calculated relative to full scale, span, or the actual reading, and to provide the corresponding technical documentation.
For specifications based on span, the span is the upper range limit minus the lower limit. For example, the span for a measurement range of 0–1 MPa is 1 MPa; for a range of 0.2–1 MPa, the span is 0.8 MPa. Although both ranges have the same upper limit, the basis used to calculate the error is different.
Also check whether the stated accuracy includes nonlinearity, hysteresis, and repeatability, and under what temperature, power supply, and installation conditions the specification was determined. Some specifications list temperature effects and long-term stability separately, so accuracy under reference conditions should not be treated directly as the total error in the field.
If the technical documentation explicitly specifies an error limit of ±0.25% of span, calculate the corresponding pressure error limit as “span × 0.25%.” Before calculating, ensure that the units are consistent and confirm that the percentage applies to the range actually ordered and calibrated.
For example, for a 0–1 MPa range with an error limit of ±0.25% of span, the calculated result is ±0.0025 MPa, or ±2.5 kPa. This expresses the allowable error limit as a pressure value within the specified reference conditions and applicable range; it does not mean that every measurement will have an error of the same magnitude.
The example below is provided only to illustrate the calculation method. Actual acceptance should be based on the accuracy definition agreed in the contract and the product technical documentation.
If the range is too large, the allowable error expressed in pressure units will increase even if the accuracy percentage remains unchanged. If the process operates for extended periods at the low end of the range, also calculate the allowable error as a proportion of the typical operating pressure to determine whether it meets control requirements.
For example, the error limit of a 0–1 MPa transmitter is ±2.5 kPa. At a measured pressure of 100 kPa, this error limit is equivalent to ±2.5% of the reading; at 500 kPa, it is equivalent to ±0.5% of the reading. This comparison uses the same absolute error limit; it does not mean that the instrument’s accuracy class has changed.
However, the range should not be made as small as possible. Before purchasing, determine the normal pressure, startup peaks, shutdown surges, and abnormal operating conditions, and check parameters such as allowable overpressure and burst pressure. The appropriate margin should be determined based on equipment design and process risks; a fixed percentage should not be applied to every application.
Some pressure transmitters allow range adjustment, but the sensor’s upper measurement limit, configurable range, and factory calibration range are not necessarily the same. Specify the required upper and lower limits, as well as the relationship between the output signal and pressure, when placing the order.
After the range is narrowed, the manufacturer’s stated accuracy may still be based on the sensor’s original range, may be calculated based on the adjusted span, or may use a piecewise formula. Do not assume that halving the range will automatically halve the absolute error limit.
For a 4–20 mA output, also confirm the specified output behavior at zero, full scale, and overrange. If the downstream acquisition module also has input error or resolution limits, include these in the overall measurement requirements rather than comparing only the transmitter itself.
Temperature changes, power supply fluctuations, installation location, vibration, and medium characteristics can all affect measurement results. Specify the ambient temperature, medium temperature, pressure type, and wetted-material requirements in the purchasing documents, then ask the supplier to confirm the applicable model and the relevant influence specifications.
For example, if the field requirement is a measurement error of no more than ±5 kPa, you cannot conclude that it will be met solely based on a stated error of ±2.5 kPa under reference conditions. Also check the zero and span temperature effects across the operating temperature range, as well as the error of the display instrument or acquisition module.
How different error components are combined depends on their definitions, correlation, and acceptance requirements. For projects requiring a conservative assessment, the error limits may first be added in the same units to produce a preliminary budget; the final conclusion should be based on the manufacturer’s data, calibration results, and specific operating conditions.
Specify the pressure reference clearly: gauge, absolute, and differential pressure refer to different measurement targets. Confirm the pressure connection specification, sealing method, and installation space during the quotation stage as well.
For corrosive, viscous, or crystallizing media, check the wetted materials, diaphragm design, and any necessary isolation measures. For high-temperature applications, also confirm the relationship between the medium temperature and the allowable temperature of the transmitter body.
For electrical requirements, confirm the power supply, current or voltage output, wiring method, and field electromagnetic interference requirements. If explosion protection or other mandatory requirements apply, verify the valid certificates and conditions of use for the specific model.
The quotation or contract should specify the pressure range, pressure reference, allowable error, operating temperature, output signal, and process connection method. For critical measurement points, also agree on the calibration range, calibration points, and acceptance criteria.
Upon delivery, check the nameplate, model, range, and documentation, and inspect the zero point, upper limit, and several intermediate points as required by the project. Where hysteresis requirements apply, check the results during both pressurization and depressurization; assess calibration results and measurement uncertainty according to the agreed method.
After the equipment is put into service, zero drift, blocked piping, leaking connections, or faults at the acquisition end can all cause reading deviations. Establishing inspection and calibration intervals suited to the operating conditions helps distinguish instrument issues from installation or process issues.
In addition to pressure measurement, applications such as batching, storage tanks, and truck scales may involve weighing or force measurement. These applications also require checks of range, combined accuracy, temperature effects, and associated instruments, but the specification definitions for load cells cannot be directly applied to pressure transmitter calculations.
For example, CXH-108 Chinese-Made Load Cell for Truck Scales, Bridge-Type Load Cell, Force Sensor for Tank and Hopper Scales can be used in force measurement and control applications such as batching scales and crane scales. Its specifications list a range of 5 kg–20 t; confirm the exact specifications, installation method, and parameter units before ordering.
Xi'an Shenghongchuang Instrumentation Co., Ltd. provides sales and technical services for sensors, transmitters, and associated instruments. When purchasing a pressure transmitter, compile the typical operating pressure, peak pressure, medium, temperature, connection, and allowable error, and have technical personnel check each item. Request accuracy specifications and calibration documentation for the corresponding range.