How to Select an Intrinsically Safe Pressure Transmitter: Matching Explosion-Proof Markings and Safety Barrier Parameters
Added to Favorites:125

When selecting an intrinsically safe pressure transmitter, whether its explosion-protection marking matches the safety barrier parameters directly affects system safety. This article outlines the key points to check.

1. First confirm hazardous area conditions and explosion-protection markings

An intrinsically safe pressure transmitter limits the voltage, current, and stored energy in its circuit so that, under specified normal and fault conditions, the equipment does not generate electrical sparks or thermal effects capable of igniting an explosive atmosphere. The safety barrier and transmitter must be assessed as a system; it is not sufficient to check whether either device carries an explosion-protection marking.

Before selecting equipment, collect information on hazardous area classification, the names of combustible substances, ambient temperature, process media temperature, and installation location. The pressure transmitter’s process connection may interface with different zones. Refer to the installation conditions in the certificate to confirm which zones each part of the equipment is suitable for.

Take “Ex ia IIC T4 Ga” as an example: “ia” indicates the level of intrinsic safety protection, “IIC” indicates the applicable gas group, “T4” indicates the temperature class, and “Ga” indicates the equipment protection level. The actual scope of use is subject to the product’s explosion-protection certificate and any special conditions for use.

What to check on explosion-protection markings

For explosive gas atmospheres, the equipment protection level generally corresponds to the zone: Ga equipment can be used in Zone 0; Ga or Gb equipment in Zone 1; and Ga, Gb, or Gc equipment in Zone 2. The complete explosion-protection marking and installation conditions must still be met. The term “intrinsically safe” alone is not enough to determine whether equipment can be installed in Zone 0.

For gas groups, IIC equipment can generally cover IIB and IIA gas atmospheres under equivalent conditions. The temperature class must ensure that the equipment’s maximum surface temperature is below the ignition temperature of the combustible substances present, and comply with applicable standards and certificate requirements.

For explosive dust atmospheres, check the applicable dust marking, equipment protection level, surface temperature, and dust-layer conditions. Do not directly apply the assessment criteria for gas atmospheres. The table below is for preliminary screening of gas atmospheres only; the project’s area classification documents and equipment certificates take precedence.

Hazardous areaCommon equipment protection levelsSelection considerations
Zone 0GaCheck whether the equipment and circuit are permitted for use in the area, as well as any special process connection requirements
Zone 1Ga or GbCheck the gas group, temperature class, and ambient temperature range
Zone 2Ga, Gb, or GcConfirm against the complete marking, certificate, and site installation conditions

2. Matching the entity parameters of the safety barrier and transmitter

The output parameters on the hazardous-area side of the safety barrier must be compared item by item with the transmitter’s intrinsically safe input parameters. Common symbols include the safety barrier’s maximum output voltage Uo, maximum output current Io, and maximum output power Po, as well as the transmitter’s maximum input voltage Ui, maximum input current Ii, and maximum input power Pi.

The basic verification relationships are Uo≤Ui, Io≤Ii, and Po≤Pi. Use the parameters specified in the explosion-protection certificates or corresponding control drawings for the terminals actually used, rather than substituting general performance parameters such as supply voltage or normal operating current.

For example, a safety barrier is marked Uo 28 V, Io 93 mA, and Po 0.65 W; the corresponding transmitter terminals are marked Ui 30 V, Ii 100 mA, and Pi 0.75 W. These three values each meet the inequalities above. This is only a preliminary assessment; capacitance, inductance, gas group, and other certificate restrictions must also be checked.

Cable energy storage must also be included in the loop

The transmitter’s equivalent internal capacitance Ci and inductance Li, together with the capacitance and inductance of the connecting cable, affect the energy stored in the loop. Typically, verify that the sum of Ci and cable capacitance Cc does not exceed the maximum external capacitance Co permitted by the safety barrier, and that the sum of Li and cable inductance Lc does not exceed the permitted external inductance Lo.

Use cable parameters provided by the manufacturer, and calculate them based on the actual cable length. For example, if the cable capacitance is 100 pF/m and the length is 200 m, the cable capacitance is approximately 20 nF. This must be compared together with the equivalent capacitance of the transmitter and other connected devices.

Note that Co and Lo may vary depending on the gas group. When external capacitance and inductance are both present, the certificate or applicable standards may require further reductions to the permitted values. Do not simply apply the calculation results for a single device to situations involving multiple connected devices or a combination of concentrated and distributed parameters.

Check itemBasic relationshipData source
Voltage, current, and powerUo≤Ui; Io≤Ii; Po≤PiExplosion-proof certificates or control drawings for the safety barrier and transmitter
CapacitanceCi+Cc≤CoEquipment certificates, cable parameters, and actual cable length
InductanceLi+Lc≤LoEquipment certificates, cable parameters, and actual cable length

3. Account for the signal, power supply, and downstream display

Meeting the explosion-protection parameter requirements does not guarantee that the pressure transmitter will operate correctly. For a two-wire 4 mA–20 mA loop, also check the safety barrier’s channel type, power-supply capacity, and output characteristics to confirm that it is suitable for the field transmitter and downstream input device.

In the engineering design, calculate the available voltage at the maximum loop current under the worst-case operating conditions specified by the manufacturer. After allowing for voltage drops across the safety barrier, cable, and other series loads, the voltage at the transmitter terminals must still meet its specified minimum operating voltage. Isolated safety barriers and zener safety barriers have different power-supply and grounding requirements; consult the respective product manuals.

For centralized display and alarms in the safe area, a digital display controller can be selected based on the output signal. For example, the DJYB-300A Chinese-made temperature detection and alarm digital display controller supports configurable input signal selection and can display and alarm on signals such as pressure. When selecting a unit, still verify its specific input configuration, power-supply specifications, and wiring method.

A digital display controller cannot replace a safety barrier

This controller has a basic error of less than 0.5% F.S., a measurement and control cycle of 0.2 seconds, and two relay alarm outputs. The accuracy of the actual system is also affected by factors such as the pressure transmitter, safety barrier, range settings, and field interference. The controller’s error must not be treated as the error of the entire measurement loop.

Whether the controller qualifies as associated apparatus for an intrinsically safe system must be confirmed by its explosion-protection certificate. Display, isolation, or alarm functions alone do not make it a safety barrier. A controller without the relevant explosion-protection certification must be installed in a safe area and connected to hazardous-area equipment through a suitable safety barrier.

If alarm contacts or other control signals need to be transmitted, the explosion-protection design of each relevant circuit must also be verified separately. The intrinsic safety assessment for one pressure measurement loop does not automatically apply to another independent output circuit.

4. Installation acceptance and documentation review

Safety barriers are typically installed in a safe area. If one must be installed in a hazardous area, confirm that the product itself has explosion-protection certification suitable for its installation location and meets the requirements specified in the certificate. Zener safety barriers have explicit grounding requirements; isolated safety barriers must also be grounded and shielded in accordance with product documentation and engineering specifications.

During wiring, maintain the specified separation or spacing between intrinsically safe and non-intrinsically safe circuits in accordance with applicable standards and design documents, and clearly label terminals and cables. Do not modify the transmitter’s internal components or wiring method, or add unapproved devices to the loop.

For acceptance, retain the area classification documents, equipment explosion-protection certificates, parameter-matching calculations, cable documentation, and wiring diagrams, and verify that the model on the nameplate matches the equipment installed. If the certificate specifies special conditions for use, implement each requirement, including those relating to ambient temperature, process temperature, and electrostatic protection.

When preparing to select equipment, provide Xi’an Shenghongchuang Instrumentation Co., Ltd. with the media name, hazardous area, pressure range, process temperature, signal type, and estimated cable length. Its technical staff can verify the parameters against the specific model, certificate, and site drawings. Final installation and acceptance should be carried out by qualified professionals.