How can a high-temperature pressure transmitter be insulated? The key is not only to reduce the process medium temperature, but also to keep the sensing element, electronic circuitry, and sealing structure continuously within their respective allowable operating ranges. Heat sinks and capillary tubes are two common solutions, but their heat transfer paths, response characteristics, and installation requirements differ, so the choice should not be based solely on the process medium temperature.
After a high-temperature process medium enters the pressure connection, heat is transferred through the fittings, metal structure, and internal pressure-transmitting medium. Even if the electronic housing does not come into direct contact with the pipe, it may exceed its temperature limit due to heat conduction, thermal radiation, or a rise in the surrounding air temperature.
When the temperature exceeds the allowable range, the pressure-sensing element may experience zero-point drift, changes in span, and reduced sealing performance. Prolonged exposure to excessive temperatures may also shorten the service life of electronic components. Normal readings over a short period do not mean that continuous operation is safe.
Therefore, during selection, separately check the process medium temperature, transmitter operating temperature, ambient temperature, and storage temperature. The maximum temperatures during equipment startup, shutdown, and process fluctuations should also be included in the assessment.
A heat sink is typically installed between the process connection and the transmitter's measuring component. By increasing the metal surface area, it dissipates some of the heat into the surrounding air. Its effectiveness depends on factors such as the heat sink design, installation orientation, airflow, and ambient temperature.
This solution is relatively compact and is suitable for operating conditions where there is some space for heat dissipation and the ambient temperature is controlled. For processes with rapid pressure changes, confirm the response performance based on the actual pressure connection structure and product specifications.
A heat sink is not a temperature-control device and cannot guarantee a fixed temperature reduction. If it is covered by insulation, placed near a high-temperature furnace wall, or installed in an enclosed area with poor airflow, its actual heat dissipation performance may be significantly reduced.
A remote capillary tube assembly typically consists of a process diaphragm, a liquid-filled capillary tube, and a transmitter. Pressure is transmitted through the diaphragm and fill fluid. The transmitter body can be installed farther from the heat source, in a location with a more suitable temperature.
A longer capillary tube is not necessarily better: its length, inner diameter, fill-fluid properties, and changes in ambient temperature may all affect response and measurement error. These effects should be carefully evaluated in applications with a low measurement range, a need for fast response, or frequent temperature changes.
The capillary tube must also be protected from bending, crushing, vibration, and exposure to heat from external sources. Damage or leakage may affect the entire sealed system, and repairs or replacement are generally more complex than with a standard direct-mount configuration.
The characteristics in the table below are general comparisons. Actual performance depends on the design, materials, and operating limits specified by the manufacturer.
If the ambient conditions at the site are relatively cool and installation space is sufficient, a heat sink configuration can be evaluated first. If the instrument must be located away from high-temperature equipment, or the process medium needs to be isolated by a diaphragm, a capillary tube solution can be evaluated further.
Whichever solution is selected, confirm the temperature and pressure ratings and material compatibility of the entire pressure boundary; checking only the transmitter body specifications is not sufficient.
For example, the PTS705 Chinese-made general-purpose rod-type air-conditioning pressure sensor lists a process medium temperature range of -30 to +85℃ and an ambient temperature range of -20 to +85℃. Applications exceeding the corresponding ranges cannot be used with standard installation methods without further evaluation.
The gauge pressure ranges listed for this model cover 0–0.01MPa to 0–250MPa, and output options include 4–20mA two-wire output. The specific range and output should be confirmed according to the order configuration; the specifications should not be interpreted as all being available simultaneously on a single product.
Wetted parts are available in 304 or 316 stainless steel, and the process medium must be compatible with the actual wetted materials. The specifications list gas, liquid, or steam applications, but steam and other high-temperature media must still comply with the temperature limits, and the suitability of the seals and connection structure must be verified.
For the PTS705, the listed temperature compensation range is 0–70℃, which differs from the allowable process medium and ambient temperature ranges. Measurement performance outside the compensation range should be assessed against the temperature drift specifications and the manufacturer's guidance.
The listed temperature drift is ≤±0.05%FS/℃, and the applicable temperature range is -20 to 85℃. This includes the temperature effects on zero and span. The project's accuracy budget should also account for temperature changes, installation method, and other sources of error.
The available specifications do not confirm which heat sink or capillary tube assembly, if any, is compatible with this model, nor do they specify the maximum process medium temperature for a combined assembly. For use beyond the original temperature range, the manufacturer should first confirm compatibility and the overall technical solution.
When installing a heat sink, reserve sufficient space for heat dissipation in accordance with the manufacturer's requirements and avoid completely covering it with insulation. Also consider thermal radiation from high-temperature pipes and furnace bodies, and assess the need for shielding and the instrument installation location where necessary.
When installing a capillary tube, secure it appropriately and keep it away from sharp edges, vibration points, and hot surfaces. If a remote diaphragm seal is used, assess the effects of static pressure based on the installation height difference, fill-fluid density, and process requirements, and calibrate it as specified by the manufacturer.
For media that solidify easily, crystallize easily, or contain particles, assess the risk of blockage in the pressure connection. For steam applications, confirm the pressure connection method based on the allowable temperature, condensation conditions, and process design; do not simply apply installation experience from other media.
Before commissioning, check the connection specifications, seals, power supply, and output signal, and confirm that the selected components' pressure ratings cover normal operating conditions and any potential pressure surges.
After commissioning, measure the temperature of relevant instrument parts and the installation environment once the equipment has reached stable operation and under typical temperature fluctuation conditions, then compare the results with the limits specified by the manufacturer. The surface temperature of a fitting cannot be used directly as a substitute for the internal sensing element temperature; consult the manufacturer for assistance with the assessment where necessary.
Xi'an Shenghongchuang Instrumentation Co., Ltd. provides pressure transmitters and related technical services. Before selecting a product, prepare the medium name, maximum temperature, pressure range, connection specifications, and photos of the installation site. Submit these to technical personnel to review the heat sink or capillary tube solution and confirm the suitability limits of the selected model and associated components.