High-temperature differential pressure sensors are commonly used in boiler steam, hot-air pipelines, metallurgical furnaces, petrochemical reaction units, heat-transfer medium circulation systems, and high-temperature gas transmission lines. In these applications, the temperature of the measured medium may reach 150°C, 250°C, or 400°C, and may be even higher under certain special operating conditions. Although differential pressure measurement reflects the pressure difference between the high- and low-pressure sides, the thermal load, static pressure load, and risk of medium corrosion actually borne by the sensor are often far greater than in ordinary pressure measurement.
A differential pressure sensor typically contains a sensing element, fill fluid, isolation diaphragm, signal conditioning circuit, and sealing structure. The electronic components and sealing materials of standard models are generally suitable for ambient or low-to-medium-temperature environments. When heat from the medium is continuously transferred to the sensor body, issues such as zero drift, sensitivity variation, degradation of fill-fluid performance, and seal aging gradually emerge.
Particularly under conditions where high temperature and high pressure coexist, a sensor does not simply need to be “temperature-resistant.” High temperatures can alter the density and viscosity of the medium within the impulse pressure path and may also cause condensate vaporization, impulse line blockage, or inconsistent liquid-column heights on the two sides. If heat-transfer conditions differ between the high- and low-pressure sides, the instrument output may exhibit significant deviation even when the actual differential pressure remains unchanged.
Therefore, the design focus of high-temperature differential pressure sensors is to keep sensing elements and electronic components within their allowable operating temperature range over the long term while ensuring true and stable pressure transmission. Remote seals and cooling measures are key structural solutions for achieving this goal.
A remote seal structure usually consists of an isolation diaphragm, flange connection, capillary tube, and sensor body. The isolation diaphragm directly contacts the high-temperature medium, and the medium pressure is transmitted to the differential pressure sensing element through the diaphragm and internal fill fluid. The sensor body can be installed farther from the pressure tapping point in a lower-temperature location, structurally reducing the direct impact of high temperatures on electronic components and the sensing element.
For media that are prone to solidification, crystallization, blockage, or that contain suspended particles, conventional impulse lines can easily cause liquid accumulation, deposits, and blockage. Remote seals use flush diaphragms or flange diaphragms directly connected to the equipment, reducing narrow and long pressure-guiding passages and making the pressure transmission path shorter and more direct. For high-temperature asphalt, resins, molten salts, slurries, and certain chemical media, this structure can significantly reduce the frequency of routine clearing and disassembly cleaning.
In differential pressure measurement, the high- and low-pressure sides should use remote assemblies of the same type and similar length. If the capillary tube lengths on the two sides differ excessively, changes in ambient temperature may cause different degrees of fill-fluid volume expansion, potentially creating an additional static pressure difference. For low differential pressure measurements with ranges of only 1 kPa, 2 kPa, or 5 kPa, this temperature effect requires particular evaluation during model selection.
A remote seal is not a fixed answer for every high-temperature application, but an engineering choice for complex media and high-temperature isolation requirements. The design should comprehensively consider medium temperature, operating pressure, differential pressure range, installation distance, ambient temperature, diaphragm material, and fill-fluid properties, rather than selecting a model based solely on the single criterion of “high-temperature resistance.”
The core purpose of cooling measures is not to reduce the medium temperature, but to prevent heat from continuously transferring to the sensor body. Common methods include installing heat-dissipation tubes, cooling bends, condensate pots, coil tubing, heat-insulation plates, and instrument protection enclosures. In steam differential pressure measurement, properly setting the impulse line length and condensation section can enable high-temperature steam to form a relatively stable condensate column before entering the instrument.
Taking saturated steam measurement as an example, if the temperature at the pressure tapping point is close to 300°C while the sensor's allowable long-term ambient temperature is only 80°C or 85°C, sufficient heat-dissipation distance must be reserved in between, and a condensation structure must be used to reduce heat transfer. In actual installation, radiation zones from furnace walls, hot-air pipelines, and high-temperature equipment surfaces must also be avoided. Otherwise, even with a properly configured impulse line, an increase in ambient temperature may still cause the instrument operating temperature to exceed its limit.
The cooling structure should also maintain consistency between the high- and low-pressure sides. Differences in condensate pot installation height, significant inconsistencies in impulse line length, or different insulation conditions on the two sides will alter liquid-column static pressure and introduce zero offset. For differential pressure transmitters used for flow measurement, small differential pressure errors are amplified into flow deviations after square-root calculation; therefore, installation symmetry cannot be overlooked.
It should be noted that stronger cooling is not always better. Excessive cooling may cause certain media to condense, increase in viscosity, or even precipitate crystals, thereby affecting pressure transmission instead. A reasonable solution should balance the sensor temperature range, medium phase stability, and response speed, and be verified in combination with continuous on-site operating time.
When selecting a high-temperature differential pressure sensor, the maximum and normal medium temperatures should first be clarified rather than providing only the equipment design temperature. For example, if the occasional equipment temperature is 350°C and the normal operating temperature is 280°C, the sensor solution must consider both continuous withstand capability and short-term temperature shock. The maximum static pressure, actual differential pressure range, medium composition, presence of solid particles, and existence of vacuum conditions should also be provided.
Range selection should take both measurement resolution and overload capacity into account. Under normal circumstances, the operating differential pressure should preferably fall within 30% to 80% of the measuring range. If the long-term operating differential pressure accounts for less than 10% of full scale, signal utilization is low, and the impact of temperature drift on measurement accuracy becomes more pronounced. For applications such as filter differential pressure and low differential pressure in air ducts, models with suitable low ranges should be prioritized, with proper installation compensation.
Diaphragm materials should be selected according to corrosion resistance and temperature rating. 316L stainless steel is suitable for most conventional industrial media, Hastelloy is more suitable for certain corrosive chemical media, and tantalum can be used in specific highly corrosive applications. Capillary tube length should not simply be made longer: increasing distance improves thermal insulation, but may also increase temperature response lag and ambient temperature error.
After installation is completed, zero-point checks, impulse pressure system leak tests, and operating temperature-rise observations should be performed. Output changes should be recorded during the initial equipment heat-up period, after stable operation, and during shutdown cooling to confirm whether pressure transmission on the high- and low-pressure sides is stable. For continuous production installations, remote diaphragms, impulse line insulation conditions, and cooling structures are recommended for inclusion in regular inspection items.
Equipping high-temperature differential pressure sensors with remote seals and cooling measures is essentially intended to isolate high-temperature media, protect sensing elements, reduce impulse line blockage, and suppress measurement errors caused by temperature changes. For high-temperature, high-pressure, corrosive, crystallizing, and high-viscosity media, a well-designed structural solution has greater practical value than simply increasing the sensor temperature-resistance rating.
Relying on the production base of Shaanxi Qinkong Sensor Technology Co., Ltd., Xi'an Shenghongchuang Instruments & Meters Co., Ltd. can provide supporting selection services for differential pressure sensors, differential pressure transmitters, remote flanges, cooling accessories, and intelligent digital display control instruments for conditions involving steam, hot air, chemical reactions, high-temperature level measurement, and industrial furnaces. Products can be customized for non-standard requirements based on measuring range, connections, diaphragm materials, output signals, and on-site installation conditions.
In industrial automation systems, stable differential pressure data is directly related to flow calculation, level control, equipment safety interlocking, and energy consumption management. Through early-stage operating condition confirmation, proper selection of remote structures, and standardized arrangement of cooling and impulse pressure systems, instrument failure rates can be effectively reduced, sensor service life can be extended, and the continuous operating capability of the entire measurement and control system can be improved.
If on-site issues such as high-temperature media, steam condensation, diaphragm coking, impulse line blockage, or differential pressure signal fluctuations are present, medium temperature, pressure range, differential pressure range, equipment connection dimensions, and installation location can be provided for targeted selection by Xi'an Shenghongchuang technical personnel and development of a remote seal and cooling installation solution.