The installation location and range selection of an air-conditioning pressure transmitter directly affect how effectively the refrigeration system is monitored. This article outlines key selection and installation considerations for project managers.
Pressure is not the same throughout an air-conditioning refrigeration system. Pressure changes at the compressor suction side, discharge side, and condenser outlet, for example, reflect the evaporation, compression, and condensation processes, respectively. Before selecting a measurement point, determine whether the signal will be used for operating monitoring, capacity adjustment, or abnormal-condition alarms.
Low-pressure-side measurements are generally used to monitor evaporation pressure, help assess the refrigerant supply condition, and provide a reference for compressor operating control. High-pressure-side measurements are commonly used to monitor condensing pressure and provide a basis for controlling the condenser fan or cooling water system.
A pressure transmitter provides a continuous measurement signal and should not simply replace independent high- and low-pressure protection devices. Protection functions involving compressor shutdown and personnel or equipment safety should be configured according to equipment design requirements, and the control system’s response to failures should be verified.
The specific connections should be determined according to the unit design drawings and equipment manufacturer’s requirements. For a unit that needs to monitor both high and low pressure, separate measurement points are generally required; a single point cannot replace pressure data from both locations.
When selecting a range, first confirm the refrigerant type, system design pressure, and possible shutdown equilibrium pressure at the highest ambient temperature. After shutdown, the pressures on the high- and low-pressure sides gradually approach equilibrium, so the low-side transmitter may also be exposed to pressures significantly higher than normal suction pressure.
The upper measurement limit should cover the highest pressure that may occur at the measurement point, with an allowance as required by the unit design. Also verify the transmitter’s allowable overpressure and burst pressure separately. Overpressure capacity applies to short-term overpressure under specified conditions and should not be used as the normal measurement range.
Pressure characteristics vary considerably among refrigerants, and the pressure of the same refrigerant also changes with temperature. Selection should be based on pressure-temperature data for the relevant refrigerant and the equipment technical documentation; the range used for another unit should not be applied directly.
For a 0–4 MPa gauge-pressure transmitter, for example, under ideal linear conditions, a 4–20 mA signal corresponds to 0–4 MPa, and 12 mA corresponds to 2 MPa. If the controller converts the signal using a different range, the displayed value and alarm points will deviate from the actual pressure.
A range that is too small may result in measurements exceeding the range and could even damage the sensor; a range that is too large reduces the ability to distinguish small pressure changes. After meeting requirements for maximum pressure, overpressure, and shutdown conditions, select an appropriate standard range.
For example, with an accuracy specification of ±0.5% FS and a range of 0–4 MPa, the full-scale error magnitude is ±0.02 MPa. If a 0–10 MPa product with the same accuracy class is used instead, it is ±0.05 MPa. This example is calculated based on full scale; actual performance also depends on temperature, long-term drift, and system error.
During project selection, it is recommended that the normal pressure range, highest possible pressure, pressure type, and required control accuracy be listed in one table and checked with the supplier. Setpoints involving safety protection should also comply with the unit manufacturer’s requirements.
The installation connection should allow easy maintenance and avoid locations where contaminants are likely to accumulate. Where piping vibration is significant, suitable pressure connections or support measures may be used as required by the equipment to reduce the direct transmission of vibration to the transmitter. The pressure rating, temperature rating, and refrigerant compatibility of the fittings should also be confirmed.
Temperatures on the discharge side may be high, so suitability should not be assessed solely based on normal-temperature data for the medium. Verify the actual medium temperature at the installation point, ambient temperature, and transient temperature changes. Where necessary, use insulation or pressure connections that meet equipment requirements to prevent operation beyond the product’s allowable conditions.
Low-temperature piping may develop condensation, while outdoor units may be exposed to rain and sunlight. When selecting a product, check its protection capability in relation to the installation orientation, connector sealing, and cable routing. The specified ingress protection rating can only be achieved with correct installation and suitable sealing.
Before wiring, confirm the output signal, supply voltage, and controller input type. Common signals include 4–20 mA and voltage signals, but wiring methods, supply ranges, and allowable loads differ between products; do not wire based on appearance alone.
Route signal cables with the site’s electromagnetic environment in mind, keeping them away from inverter power cables and equipment that generates strong interference wherever possible. Follow the transmitter and control system manuals for shielding, grounding, and cable length to reduce display fluctuations caused by interference.
During commissioning, check the connection seal and use a leak-detection method suitable for the refrigeration system. Compare the pressure readings with a calibrated reference instrument, and check the controller range, units, and alarm settings. Disassembly, installation, and maintenance should be carried out by appropriately qualified personnel in accordance with operating procedures.
In addition to the pressure range, confirm the compatibility of the refrigerant and refrigeration oil with the wetted materials and seals. Ceramic sensing elements can be used to measure a variety of media, but suitability for a particular refrigerant and operating condition must still be assessed based on the complete set of wetted materials, the sealing structure, and the manufacturer’s documentation.
During product comparison, the domestic capacitive pressure transmitter PS133 ceramic capacitive pressure transmitter for gas and hydraulic pressure sensing can be included in the products under consideration. This series uses ceramic capacitive measurement technology. Pressure acting on the ceramic diaphragm causes a change in capacitance, which is detected by the electronic components and converted into a standard signal.
The product documentation lists a compensated temperature range of −40 to +85℃ and an enclosure protection rating of IP65. Before using it in an air-conditioning system, confirm with the supplier the range, pressure type, connection, output signal, wetted materials, and allowable medium temperature for the selected configuration. Series specifications should not be assumed to apply to every configuration.
Project managers can compile the refrigerant model, measurement point location, normal and highest possible pressures, medium temperature, ambient conditions, and connection dimensions. Any shutdown high-pressure conditions, frequent starts and stops, strong vibration, or outdoor condensation should also be reported in advance.
For projects that need to connect to a building automation system or unit controller, also provide the power supply conditions, input signal type, required cable length, and display units. This helps verify the transmitter, controller, and on-site installation conditions together.
To determine the specific configuration of an air-conditioning pressure transmitter, submit the unit parameters and measurement point information to Xi'an Shenghongchuang Instrumentation Co., Ltd. Confirm range headroom, material compatibility, and installation connections before finalizing the purchasing plan.