How to Troubleshoot Zero Drift in a Diffused Silicon Differential Pressure Sensor
Added to Favorites:125

Troubleshooting Approach for Zero Drift in Diffused Silicon Differential Pressure Sensors

Diffused silicon differential pressure sensors use a silicon piezoresistive sensing element to convert the pressure difference between the high- and low-pressure sides into an electrical signal, which is then amplified, temperature-compensated, and converted into a standard measurement signal. Zero drift refers to a phenomenon in which the sensor output shifts over time, with temperature, installation condition, or external factors when the actual differential pressure should be zero or remain unchanged.

For 4mA~20mA output differential pressure transmitters, the theoretical output at zero differential pressure should normally be close to 4.000mA. If the on-site output remains significantly offset for a long period, for example, stable at 4.16mA or 3.88mA, or continuously fluctuates within a short period, it is necessary to determine whether zero drift is present. For a range of 0kPa~10kPa, a 0.16mA offset is approximately equivalent to a 0.1kPa measurement error.

During troubleshooting, the sensing element should not be assumed to be damaged directly. Installation stress, accumulated liquid in impulse lines, improper valve manifold operation, unstable power supply, poor grounding, sudden ambient temperature changes, and process medium blockage may all cause zero-point abnormalities. It is recommended to address each item in the order of “operating condition confirmation, external inspection, signal verification, zero calibration, and performance assessment.”

Xi'an Shenghongchuang Instrumentation Co., Ltd. recommends that maintenance personnel record the instrument model, range, output type, installation location, ambient temperature, current reading, and historical alarm conditions before each inspection. Complete on-site records help distinguish intermittent interference from continuous drift and facilitate subsequent calibration, factory return inspection, or replacement selection.

Step 1: Confirm Whether the Differential Pressure Is Truly at Zero

Check the Valve Manifold, Impulse Lines, and Pressure Tapping Conditions

The “zero point” of a differential pressure sensor must be established on the basis that the pressures on the high- and low-pressure sides are truly balanced. For field instruments equipped with a three-valve or five-valve manifold, first close the pressure tapping valves on both the high- and low-pressure sides, then slowly open the equalizing valve to make the pressure on both sides consistent. Any deviation observed without proper balancing is actual residual differential pressure and should not be treated as zero drift.

When measuring liquid media, focus on checking whether the liquid column heights in the impulse lines on the high- and low-pressure sides are equal. A difference of 100mm in liquid level between the two sides may create a considerable static pressure difference; this effect is particularly significant for low-range differential pressure measurement. For gas media, check whether condensate is present in the impulse lines to prevent accumulated liquid on one side from creating additional pressure head.

Under steam and high-temperature medium conditions, the installation height of condensate pots, the filling level of condensate, and the insulation conditions of impulse lines on both sides should be kept as consistent as possible. If one side dissipates heat faster, the condensate density and liquid column condition may change, causing the instrument to exhibit a gradual zero-point shift that is often related to day-night ambient temperature differences.

After blowdown and venting operations are completed, wait for the output to stabilize before recording the result. Generally, observation for 3 minutes~10 minutes is appropriate; for long impulse lines, low-range applications, or high-temperature conditions, the stabilization time may be extended as appropriate. If the output returns to normal after balancing, troubleshooting should focus on the pressure tapping system rather than the sensor itself.

Common Field Conditions and Preliminary Assessment

On-Site SymptomsPriority Inspection ItemsRecommended Action
The reading returns to zero after the equalizing valve is openedWhether there is an actual differential pressure between the high- and low-pressure sidesCheck valve manifold operation and process pressure tapping conditions
The reading slowly drifts in one directionCondensate accumulation, leakage, blockage, or temperature changesClear the impulse lines and verify the liquid columns on both sides
The reading fluctuates irregularly between high and low valuesVibration, electromagnetic interference, or wiring contact issuesCheck shielding, grounding, and mounting conditions

Step 2: Check Installation, Environment, and Mechanical Stress

Eliminate False Zero Drift Caused by Installation

Deformation of mounting brackets, stress from connecting piping, or forced twisting of the sensor housing may transmit mechanical stress to the sensitive structure through the diaphragm seat or fittings. Especially for products with a low differential pressure range, even slight tension from external piping may cause zero-point changes. During inspection, observe the output difference before and after piping stress is removed.

The instrument should be installed in a location with relatively low vibration and convenient maintenance access. Continuous mechanical vibration may cause connector loosening, unstable solder joint contact, or fastener fatigue, resulting in irregular output fluctuations. For measurement points near pumps, compressors, and fans, secure brackets should be used and vibration-reduction measures should be added according to operating conditions.

Although diffused silicon sensing elements are normally temperature-compensated, their zero point can still be affected by rapid ambient temperature changes. When a sensor is exposed for a long period to sunlight, thermal radiation, air-conditioning outlets, or areas adjacent to high-temperature equipment, day-night temperature differences may exceed 20 degrees Celsius, causing corresponding changes in output zero point. Check whether the instrument requires sun shading, thermal insulation, or relocation to a location with more stable temperature.

Humid environments, corrosive gases, and condensation may also affect the insulation performance of junction boxes, terminals, and circuit boards. Check whether housing sealing rings, cable sealing fittings, and terminal covers are intact. If water ingress, oxidation, or white crystallization is found, disconnect the power first for handling and replace damaged parts to prevent further expansion of the fault.

Step 3: Verify the Power Supply, Output Loop, and Interference Resistance Conditions

Identify the Source of Output Offset from the Electrical Side

For two-wire 4mA~20mA differential pressure transmitters, use a multimeter to measure the actual supply voltage at the sensor terminals rather than only checking the rated power supply value in the control cabinet. The common supply voltage is 24VDC, but long cables, terminal oxidation, or excessive loop load may cause voltage drops. When the power supply is below the allowable product range, the instrument may experience limited output, drift, or communication abnormalities.

Check whether wiring terminals are loose, crimp connections are secure, and cable insulation is damaged. Especially for outdoor equipment and long-term vibration applications, increased contact resistance may cause signal fluctuations. Retighten the terminals with power disconnected, and confirm that positive and negative polarity, shielding connection method, and the product wiring diagram are consistent.

Signal cables should be kept as far as possible from variable-frequency drives, motor power cables, welding machines, and high-power switching equipment. Although 4mA~20mA loops have strong interference resistance, interference may still be introduced when shielding is grounded at multiple points or signal cables are laid in parallel with power cables over long distances. Normally, it is recommended to ground the shielding at one end only, with the grounding point located on the control cabinet side, while ensuring continuous and reliable grounding.

When abnormal readings occur on field indicators, PLCs, or DCS systems, use a standard ammeter connected in series at the sensor output terminal for measurement. If the sensor output is stable but the upper-level system display drifts, the problem is usually in the signal loop, isolator, acquisition module, or software range setting. If the current at the sensor terminal itself changes, continue checking the instrument body and process conditions.

Electrical Inspection Reference Table

Inspection ItemNormal Reference ConditionPossible Effects of Abnormalities
Supply voltageCompliant with nameplate specifications, commonly 24VDCOutput limitation, zero-point variation, or communication interruption
Zero OutputClose to 4.000mA at zero differential pressureThe range setting must be distinguished from sensor drift
Shielding and groundingIntact shielding with reliable single-end groundingPower-frequency or variable-frequency interference causes signal fluctuations

Step 4: Properly Perform Zero Calibration and Performance Confirmation

Determine Whether Conditions for Zero Calibration Are Met First

Zero calibration can only be performed after confirming that the high- and low-pressure sides are balanced, the impulse lines are in normal condition, and the power supply is stable. For smart differential pressure transmitters with local buttons or a handheld communicator, enter the zero adjustment menu according to the product instructions; analog products should use the corresponding zero adjustment mechanism. Do not forcibly calibrate the zero point while an actual pressure difference still exists between the two sides, otherwise the process error will be written into the instrument.

After zero calibration, it is recommended to use a standard pressure source or differential pressure calibrator to verify no fewer than 3 test points, such as 25%, 50%, and 75% of range. For a range of 0kPa~10kPa, 2.5kPa, 5.0kPa, and 7.5kPa can be applied respectively to observe whether the output corresponds to the theoretical values and confirm that zero point, linearity, and repeatability are all within the allowable error range.

If normal operation is restored shortly after zero calibration but significant offset occurs again within several hours or days, external operating conditions, temperature changes, impulse line leakage, or decreased internal stability should be suspected. A single calibration can only correct the current zero point and cannot replace elimination of the fault cause. Calibration data before and after adjustment should be retained to determine drift rate and trend.

If the instrument zero point cannot be adjusted, full-range output is insufficient or exceeds limits, the zero return after repeated pressurization is inconsistent, or drift continues to increase in a stable environment, the issue may involve sensing element aging, isolation diaphragm damage, filling fluid abnormalities, or circuit faults. In such cases, stop repeated forced calibration and contact professional technical personnel for inspection, repair, or replacement.

Recommendations for Routine Maintenance and Fault Handling

Establish a Traceable Preventive Maintenance Mechanism

For critical measurement points, it is recommended to establish a regular inspection system, focusing on recording zero output, process readings, supply voltage, ambient temperature, and impulse line condition. Under normal operating conditions, functional inspections can generally be performed every 3 months~6 months; for high-temperature, corrosive, crystallization-prone, high-vibration, or frequent start-stop conditions, the inspection interval should be shortened based on actual risk.

During maintenance, avoid using hard objects to directly contact the isolation diaphragm. Do not blow high-pressure gas into the pressure port or use incompatible cleaning agents. For viscous, clogging-prone, or particle-containing media, configure isolation devices, flushing connections, or suitable pressure guiding methods according to process conditions to reduce the risk of blockage and diaphragm damage.

During product selection, the rated differential pressure range should match actual operating conditions. If the selected range is too large, small differential pressure changes are compressed and minor zero-point offsets become more apparent; if the range is too small, it is easily affected by impact differential pressure. Product parameters can generally be determined comprehensively based on normal operating differential pressure, maximum differential pressure, static pressure rating, medium temperature, and corrosiveness.

Xi'an Shenghongchuang Instrumentation Co., Ltd. can provide diffused silicon differential pressure sensors, differential pressure transmitters, intelligent digital display control instruments, and supporting services for non-standard operating conditions for differential pressure measurement projects. If continuous zero drift occurs on site, please prepare a photo of the instrument nameplate, range information, wiring method, installation diagram, and calibration data, then contact technical service personnel for targeted diagnosis and handling.