Pressure Transmitter Manufacturer
Consultation hotline:15529283736
News Center
—— NEWS CENTER ——
Xi'an Shenghongchuang Instrument Co., Ltd.
Contact: Mr. Zhang
Mobile: 15529283736
Email: shc-sensor@qq.com
Address: Fortune Building, Sanqiao Street, Xixian New Area, Xi'an, Shaanxi Province
In low-pressure water supply systems, if a pressure transmitter with a lower range limit below 0.1MPa (that is, 100kPa) is selected, its actual output signal is easily affected by disturbances such as temperature fluctuations, installation stress, and minor medium interference, resulting in insufficient resolution in the small-signal section and poorer repeatability, which in turn may trigger false control actions or distorted data recording. This issue is not about whether the nominal accuracy value meets the standard, but about the fact that after the physical measurement boundary is compressed, the proportion of the sensor's inherent noise rises significantly.
This issue is important because water supply systems are extremely sensitive to pressure fluctuations—even a misjudgment of 0.02MPa may trigger frequent pump starts and stops, intensified cavitation, or water hammer in the pipeline network. To determine whether it is suitable, priority should be given to confirming whether the system's minimum steady-state operating pressure remains continuously higher than 15% of the selected transmitter's lower range limit, rather than merely checking whether the nominal range covers "0~0.1MPa".
The zero-point error of a pressure transmitter is usually expressed as a percentage of full scale (%FS), for example ±0.25%FS. When the range is 0~0.1MPa, ±0.25%FS corresponds to an absolute error of ±0.00025MPa; but if the actual operating pressure is only 0.03MPa, this error already accounts for 0.83% of the measured value. The error proportion increases exponentially as the measured pressure decreases.
More importantly, the nonlinearity of silicon piezoresistive sensing elements becomes more pronounced in the low-pressure section, and slight diaphragm deformation is easily affected by mechanical factors such as gravity direction, thread tightening torque, and pipeline vibration. These influences cannot be completely eliminated through conventional calibration below 0.1MPa.
Whether a higher accuracy class is needed mainly depends on the response threshold of the control logic to pressure changes. If the PLC is set to "start the booster pump when pressure falls below 0.04MPa", then the transmitter's actual measurement error at the 0.04MPa point must be less than ±0.001MPa. In this case, the lower range limit should not be below 0.06MPa.
Scenarios such as terminal points of secondary water supply in old residential communities, gravity-fed rooftop water tanks, outlets of non-negative pressure water supply equipment, and downstream sections after constant-pressure make-up water valves often have static pressure in the 0.02~0.06MPa range and are accompanied by periodic pulsation. Under such conditions, the transmitter works for a long time within the leftmost 10% of the range, accelerating diaphragm fatigue, and the annual drift rate may reach 2~3 times the nominal value.
A common practice is to shift the lower range limit upward to 1.2~1.5 times the system's minimum steady-state pressure. For example, if the measured minimum static pressure at the terminal is 0.045MPa, then 0~0.07MPa or 0~0.1MPa is preferred, rather than 0~0.05MPa.
What truly affects the result is not whether the transmitter can output a numerical value, but whether the credibility of that value in the control decision chain can continuously meet requirements. If the system allows a pressure fluctuation of ±0.01MPa, then the actual measurement uncertainty of the selected transmitter in the corresponding interval must be better than ±0.003MPa.
Ultra-low-range transmitters are prone to a "hard-to-stabilize zero point" phenomenon during field commissioning: a slight tap on the housing, a 1℃ change in ambient temperature, or even a change in cable bending radius may cause the output to jump by 0.5~2mA. This can mask real faults, causing maintenance personnel to misjudge the issue as loose wiring or power supply interference.
After long-term operation, the zero-point calibration interval needs to be shortened to 3~6 months, far higher than the 12-month interval of conventional 0.1~1MPa range products. If recalibration is not carried out at this frequency, the accumulated zero drift after 6 months may exceed ±0.002MPa, surpassing the deadband setting of most PID controllers.
Whether periodic recalibration needs to be scheduled in advance depends on the system's tolerance for pressure continuity. For fire protection pressure-stabilizing systems, this error may directly cause invalid starts and stops of the pressure-stabilizing pump; for domestic water metering, it may lead to accumulated deviation in flow totalization.
Feasible approaches include switching to a differential pressure transmitter with pressure tapping pipelines, adopting a dual-range switching design, or adding a pressure-stabilizing chamber in the pipeline to enlarge the effective pressure difference. Among them, the differential pressure solution requires ensuring that the elevation difference of the positive and negative pressure chamber tapping points is controllable to avoid introducing new errors from liquid column static pressure; dual-range switching depends on whether the controller supports analog input switching logic, which increases system complexity.
A more common approach is to accept the resolution loss caused by a slightly higher range in exchange for long-term stability. For example, selecting a 0~0.16MPa range instead of 0~0.05MPa reduces the resolution at the 0.04MPa point by about 20%, but improves zero-point stability by more than 3 times, resulting in higher overall reliability.
Whether this step should be brought forward depends on whether the existing control system supports range shift configuration. If the PLC analog module only supports fixed range mapping, then the compatibility of the signal conversion logic must be verified simultaneously before replacing the transmitter.
The key to judging which option is more suitable is whether the system has a steady-state pressure section continuously below 0.03MPa. If yes, priority should be given to considering a 0.06~0.09MPa lower range limit together with pressure-stabilizing measures; if it only drops below this value during instantaneous pulsation, a model with a lower limit of ≥0.1MPa can be selected directly.
Xi'an Shenghongchuang Sensor Co., Ltd. can provide stepped low-pressure range products such as 0~0.07MPa, 0~0.1MPa, and 0~0.16MPa, and supports targeted optimization such as zero-point shift, digital filtering, and temperature compensation. Its 7000-square-meter factory is equipped with independent low-pressure calibration stations, enabling multi-point live validation starting from the 0.01MPa point, but this service needs to be clearly requested during the order confirmation stage.
Immediately obtain a continuous 72-hour pressure record of the pipeline section where it is installed, with重点标注持续时间>10分钟的最低压力值,以此作为量程下限设定的基准依据。
Related Recommendations