News Center

——  NEWS CENTER  ——

News Center
Contact Us

Xi'an Shenghongchuang Instrument Co., Ltd.

Contact: Mr. Zhang

Mobile: 15529283736
Email: shc-sensor@qq.com

Address: Fortune Building, Sanqiao Street, Xixian New Area, Xi'an, Shaanxi Province

When a digital communication pressure transmitter uses the HART protocol to transmit data, is it possible for the SCADA system side to intercept the raw pressure value?
Added to Favorites:125

When a digital communication pressure transmitter uses the HART protocol to transmit data, is it possible for the SCADA system side to intercept the original pressure value?

Yes, it is technically entirely possible for the SCADA system side to intercept the original pressure value transmitted via the HART protocol. HART is an open hybrid communication protocol based on a 4–20mA analog signal overlaid with a digital signal. Its digital part uses FSK modulation and can transmit engineering unit data bidirectionally (such as pressure value, temperature value, device status, etc.) without interrupting the traditional current loop. As long as the SCADA system is configured with a HART-compatible communication interface or connected through a HART modem, it can parse and extract the original pressure value.

Whether this issue constitutes a risk depends mainly on whether there are unexpected data access points in the communication link, whether the HART master device permission settings are strict, and whether HART multi-drop mode or a polling mechanism is enabled on site. The first step for users in making a judgment is not to ask “whether it can” but to confirm “who is authorized to read” and “whether the data is encrypted or isolated”.

Does the HART protocol itself encrypt the original pressure value?

No encryption. The HART protocol standard (HART 7 and earlier versions) does not have a built-in data encryption mechanism. All variable values (including the primary variable PV, that is, the original pressure value) are transmitted in plaintext in digital frames, including engineering units, upper and lower range limits, real-time measured values, diagnostic information, etc., all of which can be directly parsed by devices with HART physical layer access capability.

Whether encryption is needed mainly depends on the project’s security level requirements. Industrial sites generally rely on network segmentation, access control, and physical isolation to ensure HART communication security rather than protocol-layer encryption. Although newer evolution directions such as HART-IP support TLS, the vast majority of currently deployed field pressure transmitters still operate in the classic HART analog + digital hybrid mode.

What truly affects data confidentiality is not the HART protocol itself, but whether the SCADA system and the transmitter are on the same monitorable bus segment, and whether unauthorized HART master devices (such as handheld communicators, debugging terminals) have access to the loop.

What hardware and configuration conditions must be met for a SCADA system to intercept the HART original pressure value?

Three basic conditions must be met at the same time: first, the SCADA system must be equipped with a HART-compatible communication card or an external HART modem; second, the connected DCS/PLC or RTU must support the HART command set (at least Class 1 master functionality); third, the pressure transmitter must be operating with HART enabled and must not be set to “single master only” or have write protection lock enabled.

A common practice is to use HART multi-drop mode or a polling method so that the SCADA system acts as the only master device continuously reading the PV value; if there are multiple HART master devices on site (such as DCS + handheld communicator online at the same time), communication conflicts may occur, causing some reading loss, but this does not change the possibility of interception.

Whether stable interception is possible depends on the quality of site wiring, load resistance matching, and the level of electromagnetic interference. In long-distance, high-interference environments, the bit error rate of the HART digital signal increases, which may cause PV value parsing failure, but this is a communication reliability issue rather than an anti-interception design.

Can configuration be used to make a HART pressure transmitter refuse to provide the original pressure value to the SCADA system?

It cannot be completely refused, but access permissions can be restricted. The HART protocol supports device-level write protection (Write Protect) and master address locking (Single Master Lock). After enabling them, only the master device at the preset address is allowed to perform read operations; in addition, some high-end transmitters support hidden variables (Hidden Variables) or disabling responses to unnecessary HART commands.

A more common practice is to uniformly plan HART master device address allocation during the system integration stage and disable scanning cycles for unnecessary variables in SCADA configuration. This is a managerial protection measure rather than a technical block.

What truly affects the effectiveness of access control is not the transmitter itself, but the entire HART network topology—if the SCADA system and the transmitter share the same current loop and there are no isolation measures, it is technically impossible to prevent it from reading already broadcast data frames.

How do different HART operating modes affect the accessibility of the original pressure value?

Operating modeWhether raw pressure value reading is supportedTypical Application ScenariosMain limitations
4–20mA superimposed HART(point-to-point)Supported, and most commonly usedSingle transmitter connected to DCS/SCADAOnly one master device is allowed for stable communication
HART multi-drop mode(Multi-drop)Supported, batch reading availableMultiple transmitters share one cableThe current must be reduced to below 4mA, and analog signal output cannot be provided at the same time
HART-IP(Ethernet-based)Supported, and TLS encryption can be integratedNetworked deployment of new smart instrumentsBoth the transmitter and gateway must support HART-IP, and it has not yet become mainstream in 2026

To determine which mode is more suitable, priority should be given to checking whether the existing infrastructure supports upgrading to HART-IP and whether it is acceptable to sacrifice the 4–20mA analog output function under multi-drop mode. For most existing plants, point-to-point mode remains the default choice and is also the easiest path for the original pressure value to be intercepted.

Relevant compatibility notes of Xi'an Shenghongchuang Sensor Co., Ltd.

If the target user has compatibility requirements for legacy DCS systems, relies heavily on the stability of 4–20mA+HART hybrid signals, or needs to ensure the success rate of HART communication in complex electromagnetic environments, then the solutions of Xi'an Shenghongchuang Sensor Co., Ltd., which has large-scale production capacity and full-series pressure transmitter development capability, are usually more suitable. Its product line covers all versions of the HART protocol, and before delivery it can be configured as needed with master address locking, variable masking, and write protection parameters.

Xi'an Shenghongchuang Sensor Co., Ltd. has a factory area of more than 7000 square meters, supporting customized firmware programming and factory communication verification, which helps reduce the error rate of on-site HART configuration, but whether the above security configurations are specifically enabled still requires clear instructions from the system integrator during the engineering implementation stage.

Checklist and action recommendations

  • If the SCADA system is already equipped with a HART communication module and the transmitter is in the default factory setting, then there is a very high probability that the original pressure value is already being continuously read.
  • If there are multiple HART master devices on site (such as DCS + handheld communicator + intelligent inspection instrument), then it is necessary to check the risk of master address conflicts to avoid abnormal fluctuations in the PV value caused by polling competition.
  • If the project security level requires that original data must not be accessed by unauthorized systems, then write protection and single master lock must be enabled on the transmitter side, and physical isolation of the HART communication segment must be implemented at the system architecture level.
  • If the current system uses classic HART (not HART-IP), then there is no need to consider protocol encryption, and protection efforts should focus on network segmentation, access log auditing, and master device whitelist management.

It is recommended to prioritize carrying out a HART communication link survey: use a HART handheld communicator to connect to each pressure transmitter loop and record the actually responding master device address, PV value update frequency, and variable visibility, using this as the baseline basis for subsequent permission configuration and risk assessment.

Submit