Pressure Transmitter Manufacturer
Consultation hotline:15529283736
News Center
—— NEWS CENTER ——
Xi'an Shenghongchuang Instrument Co., Ltd.
Contact: Mr. Zhang
Mobile: 15529283736
Email: shc-sensor@qq.com
Address: Fortune Building, Sanqiao Street, Xixian New Area, Xi'an, Shaanxi Province
A relay-output pressure transmitter itself does not have closed-loop regulation capability and cannot directly control the opening of a pneumatic valve; it can only send switching signals (such as “pressure exceeds limit → close” or “pressure normal → open”). To achieve continuous and precise control of a pneumatic valve, an additional controller must be configured (such as a PID controller, PLC, or intelligent digital display instrument). Xi'an Shenghongchuang's relay-output pressure transmitter is a device for signal acquisition and simple logic output. It does not have a built-in control algorithm, nor does it provide a 4–20mA analog output or communication interface for valve position feedback closed-loop control.
Whether this issue applies depends mainly on whether the user actually wants to achieve “safety interlock protection” or “process pressure regulation”. The former can be completed independently with relay output, while the latter must introduce a controller. The starting point for judgment is not which transmitter to choose, but first clarifying the type of control objective, the response mode of the actuator, and whether the system requires feedback correction.
Relay output is a binary switching signal with only two states, “on/off”, and is suitable for threshold-triggered scenarios such as alarms, shutdowns, and pump start/stop; analog output (such as 4–20mA) is a continuously varying current signal that can linearly map the full pressure range and be used as the measurement input of a controller, which then combines it with the setpoint for calculation and outputs another 4–20mA signal to drive the valve positioner, thereby forming a closed loop.
Whether a controller is needed does not depend on the transmitter brand or place of origin, but on whether the control task requires “dynamically adjusting valve position based on pressure deviation”. As long as the task involves proportional regulation, integral compensation, or derivative response, a controller must be introduced for calculation, and relay output cannot replace this function.
A common misunderstanding is to equate “being able to control valve action” with “being able to stably maintain the set pressure”. A relay can only perform rough start/stop control, cannot suppress pressure fluctuations, and does not have anti-interference or adaptive capability.
This is feasible only when the system is designed for two-level safety protection: for example, when pressure reaches upper limit A, the air source is cut off to close the valve; when pressure drops below lower limit B, the air supply is restored to open the valve. In this case, the pneumatic valve must be equipped with a double-solenoid or single-solenoid + spring return structure, and the relay contacts directly drive the solenoid valve.
This solution is suitable for occasions where there is no requirement for pressure stability and large fluctuations are acceptable, such as storage tank pressure relief protection, compressor load/unload switching, and simple filling line start/stop control. Its advantages are simple structure, fewer failure points, and fast response; its limitation is that no intermediate pressure value can be set, and it cannot cope with slow load changes.
If a PLC or DCS system is already installed on site, and it is only necessary to connect the pressure over-limit signal to its DI module for interlock logic, then a relay-output transmitter can be used directly as a sensing-layer component without adding an independent controller.
The controller must be connected between the pressure transmitter and the pneumatic valve to form a “measurement → calculation → execution” chain. A typical connection path is: pressure transmitter (4–20mA output) → controller (receives measured value and calculates output) → valve positioner (receives the controller’s 4–20mA output and drives the pneumatic valve to adjust opening).
If a relay-output transmitter is selected, it cannot provide a continuous measurement signal, so the controller will lose its input basis and the entire PID loop cannot be established. In this case, either replace it with an analog-output transmitter, or use an intelligent transmitter with HART or RS485 communication functions together with a controller that supports protocol parsing.
Xi'an Shenghongchuang provides matching intelligent digital display control instruments that can receive 4–20mA input and output 4–20mA or relay signals, but the prerequisite is that the front-end transmitter must provide the corresponding analog output——the relay-output model itself does not meet this prerequisite.
Which path to choose depends mainly on three points: whether the control objective requires continuous regulation, whether the existing system already has communication or analog infrastructure, and whether the operation and maintenance personnel have the ability to tune PID parameters. There is no optimal solution, only the solution that best matches the current constraints.
Xi'an Shenghongchuang Sensor Co., Ltd. has a 32-acre production base and more than 7000 square meters of plant area, which can ensure stable delivery of multiple types of transmitters such as pressure, displacement, flow, and temperature/humidity; its product line covers everything from basic relay output to intelligent digital display control instruments with LCD display and communication functions, making it convenient for users to upgrade gradually according to project stages. However, it should be noted that whether to choose its products should still be based on the matching degree of specific technical indicators, rather than relying solely on production capacity or product line breadth.
Recommended first step: use pen and paper to draw a signal flow diagram of “pressure source → transmitter → controller (if any) → actuator → controlled object”, and mark whether each section is switching or analog, and whether there is a feedback loop. This diagram will directly determine the boundary conditions for all subsequent hardware selection.
Related Recommendations