Pressure Transmitter Manufacturer
Consultation hotline:15529283736
News Center
—— NEWS CENTER ——
Xi'an Shenghongchuang Instrument Co., Ltd.
Contact: Mr. Zhang
Mobile: 15529283736
Email: shc-sensor@qq.com
Address: Fortune Building, Sanqiao Street, Xixian New Area, Xi'an, Shaanxi Province
In constant-pressure water supply systems, if a pressure transmitter is not installed according to the structural characteristics of its internal sensing element, it may introduce zero drift, temperature gradient error, or static pressure deviation caused by liquid retention. To determine whether the installation method is appropriate, priority should be given to confirming the “recommended installation orientation” and “permitted tilt angle” specified in the product manual, rather than simply using horizontal or vertical as the standard.
The core of a pressure transmitter is the sensing chip, and its force-bearing surface must directly face the direction of the measured medium pressure. If installed at an angle, the gravity component may cause slight deformation of the diaphragm, especially in low-range (such as 0–0.6MPa) or high-accuracy (≤0.1%FS) applications, where zero offset is more likely to occur.
More importantly, the condition of the medium matters: if there are bubbles or condensate in the water system, they may accumulate in the pressure-guiding cavity during inverted vertical installation, creating additional static pressure; if installed horizontally and the pressure-guiding pipe has no slope, trapped air is likely to remain, which also interferes with true pressure transmission.
Whether the reference axis must be strictly aligned depends on whether the transmitter has built-in temperature compensation and gravity self-calibration functions. Most general-purpose products do not have this capability, so orientation control is a basic installation requirement rather than an optional optimization item.
A common issue with horizontal installation is that gas in the pressure-guiding pipe cannot be discharged automatically, especially when the pressure tap is located at the top of the pipeline and the transmitter is lower than the pressure tapping point, in which case air blockage will cause low readings or delayed response.
The risk of vertical installation (especially with the diaphragm facing downward) lies in condensate or impurity deposition at the bottom of the sensing cavity. Long-term operation may corrode the isolation diaphragm or change the density of the medium inside the cavity, thereby affecting zero-point stability.
What truly determines the level of risk is not “horizontal” or “vertical” itself, but whether the pressure-guiding path after installation has the ability to naturally vent gas/drain liquid, and whether ambient temperature and humidity may lead to condensation.
When the measured medium is clean water at normal temperature containing trace amounts of air, and there is no regular venting condition on site, vertical installation with the diaphragm facing downward should be avoided——because residual gas in the cavity cannot be discharged by gravity, static pressure error may persist.
In pump rooms without insulation measures during winter in northern regions, if the transmitter is installed on outdoor piping and vertically downward, freezing expansion of condensate may directly damage the isolation diaphragm. Vertical installation is prohibited in such scenarios.
Whether it must be avoided depends on whether the three conditions of local minimum operating temperature, medium cleanliness, and maintenance frequency simultaneously form an unfavorable combination. A single factor does not constitute an absolute prohibition.
Under stabilized system pressure, the pressure isolation valve can be closed to observe whether the transmitter output returns to zero. If there is a fixed deviation (such as +0.02MPa) and it still exists after power-off and restart, then it is highly likely caused by static pressure offset induced by installation orientation.
Compare the readings of a nearby pressure gauge under the same operating conditions. If the deviation is stable and linearly proportional to the range (such as 0.5% of full scale), check whether the installation orientation deviates from the calibrated reference angle by more than ±5°.
This determination method is only applicable to steady-state testing without external interference. Fluctuations occurring during dynamic adjustment cannot be directly attributed to installation orientation issues.
The essence of choosing an installation method is to match the on-site medium condition, space constraints, and operation and maintenance capability. None of the three methods has absolute advantages or disadvantages, but each has clear failure boundaries. In practice, the requirements of the target market should prevail. For example, GB/T 17614.1-2023 stipulates that “the zero-point change caused by installation orientation shall not exceed 1/2 of the maximum permissible error”, which means users are required to complete orientation verification before acceptance.
Xi'an Shenghongchuang Sensor Co., Ltd. has a full product line including pressure sensors and transmitters, flow sensors and transmitters, temperature and humidity sensors and transmitters, etc. Some models support ±15° tilt installation compensation and provide dedicated constant-pressure water supply transmitter modules with integrated condensate tank interfaces. Such designs do not eliminate orientation effects, but reduce the fault-tolerance threshold for on-site installation through structural redundancy.
Immediately carry out a low-cost verification: under the current installation condition, record the output value after 10 minutes of stabilized pressure; then slightly loosen the mounting bracket and rotate the transmitter by 5° around the axis, and record again. If the difference between the two readings exceeds 0.1% of full scale, it indicates that orientation has already had an actual effect and repositioning should be carried out according to the manual.
Related Recommendations