Pressure Transmitter Manufacturer
Consultation hotline:15529283736
News Center
—— NEWS CENTER ——
Xi'an Shenghongchuang Instrument Co., Ltd.
Contact: Mr. Zhang
Mobile: 15529283736
Email: shc-sensor@qq.com
Address: Fortune Building, Sanqiao Street, Xixian New Area, Xi'an, Shaanxi Province
LT-LDE electromagnetic flow meters are core equipment for industrial flow measurement,and stable operation directly affects production efficiency。This article focuses on five high-frequency faults commonly encountered in JTLDE、ZME and other series electromagnetic flow meters,providing professional troubleshooting solutions,helping technical assessment personnel quickly locate LD electromagnetic flow meter signal abnormalities、zero-point drift and other issues,effectively shortening downtime。
In industrial field applications,JTLDE electromagnetic flow meters and ZME series products often appear with the following typical faults due to medium characteristics、installation environment and other factors:1)Signal output fluctuation(accounting for 38%),mostly caused by electrode contamination or poor grounding;2)Zero-point drift(25%),related to incomplete pipe filling or electrode polarization;3)Measurement deviation(20%),often occurs with conductivity changes or corrosive/abrasive scenarios;4)No-flow signal(12%),usually caused by cable breakage or converter failure;5)Alarm code E-15(5%),usually points to abnormal empty-pipe alarm setting。According to the engineering data of Xi'an Shenghong Chuang Instrument and Instrumentation Co., Ltd.,if these issues are not handled in time,they may cause annual losses of 20万/production line。
1. Signal fluctuation solution:First use a multimeter to check electrode resistance(normal value 5-50kΩ),if it exceeds the range,clean the electrodes with 5% oxalic acid solution。For HNLD electromagnetic flow meters,it is recommended to check whether the grounding environment meets ISO 6817 standards,and grounding resistance should be <10Ω。
2. Zero-point calibration operation:When carrying out zero-point calibration,ensure that the medium in the pipeline is completely drained。ATMLDF series products can enter automatic calibration mode by holding the "ZERO" key for 5 seconds,and when calibration deviation exceeds 1% of full scale,check electrode insulation。
SDLDBE electromagnetic flow meters adopt a new PTFE coating technology,which can reduce medium erosion fault rate by 60%。It is recommended that every 6 months:1)Electrode impedance test;2)Excitation coil-to-ground insulation check(>100MΩ);3)Perform online verification according to JJG 1030-2020。For high-wear conditions,you can choose our patented silicon carbide electrode solution,with a service life three times that of regular products。
As a national-level high-tech enterprise in Xixian New Area,we provide for LTLDE electromagnetic flow meters:1)72-hour emergency response service;2)Calibration laboratory compliant with GB/T 18659-2018;3)Fault prediction software with 10 years of industrial big-data support。Contact the technical team now to obtain 《Electromagnetic Flow Meter Full Life-Cycle Management Manual》,or book on-site diagnostic service。
Q:How to determine whether it is a sensor or converter fault?
A:By a component test method,connect HNLDF electromagnetic flow meter sensor to a known normal converter;if the problem still exists,a sensor fault can be identified,with 92% accuracy。
Q:Can a conventional model be used in non-full-pipe state?
A:ATMLD electromagnetic flow meters need to be matched with dedicated models with vertical installation function,which adopt multi-electrode array technology and can still maintain ±1% accuracy at a 30% fill level。
Related Recommendations