Pressure Transmitter Manufacturer
Consultation hotline:15529283736
Product Center
—— Product Center ——
Xi'an Shenghongchuang Instrument Co., Ltd.
Contact: Mr. Zhang
Mobile: 15529283736
Email: shc-sensor@qq.com
Address: Fortune Building, Sanqiao Street, Xixian New Area, Xi'an, Shaanxi Province
Xi'an Shenghongchuang Instrumentation Co., Ltd.
Contact: Mr. Zhang
Mobile: 15529283736
Email: shc-sensor@qq.com
The capacitive intelligent pressure/differential pressure/level transmitter is a high-precision intelligent instrument product independently researched, developed, and manufactured by our company on the basis of many years of scientific research and practical experience.
The intelligent pressure/differential pressure/level transmitter is a new generation of intelligent transmitter produced by adopting a sensor core manufactured with ROSEMOUNT technology and integrating the advanced digital technology developed by our company. In principle, it uses a direct digital capacitance circuit to replace the analog signal amplification circuit and A/D conversion circuit, and applies digital compensation technology to compensate for temperature and static pressure, thereby improving measurement accuracy and reducing temperature drift. The complete transmitter features small size, high reliability, and good long-term stability. With its extremely high cost performance, this product has become a mainstream product in the transmitter market.
This intelligent pressure/differential pressure/level transmitter features a novel design principle, complete varieties and specifications, convenient installation and use, and safety explosion-proof performance. It is especially well known for high accuracy, small size, light weight, convenient adjustment, good long-term stability, strong one-way overload protection capability, and suitability for use in harsh environments. Therefore, it enjoys a high reputation in both domestic and international markets. This series of 0.1 grade capacitive intelligent transmitters includes pressure, differential pressure, absolute pressure, remote transmission, level, and many other types, and is equipped with corresponding optional products. It can be widely used in electric power, metallurgy, petrochemical, instrument processing, and other industries, and complies with the "IEC" standard requirements implemented in China.
Product Features
·The use of a microprocessor provides greater flexibility and enhanced functions;
·Has strong self-diagnostic capability;
·Wide measuring range coverage 0~0.2kPa…10MPa;
·Accuracy up to 0.1 grade, turndown ratio better than 40:1;
·Zero point and span adjustment do not affect each other;
·Supports both remote and local adjustment of range and zero point;
·Two-wire system, compliant with HART protocol, capable of digital communication with ROSEMOUNT275 and MS-H376 handheld communicators without interrupting analog output;
·Sensor built-in non-volatile memory;
·Good stability, high accuracy, adjustable damping, and strong resistance to one-way overload;
·No mechanical transmission parts, low maintenance workload, sturdy and vibration-resistant;
·All universal parts, interchangeability of sensor and electronic circuit board does not affect transmitter performance, making maintenance more convenient;
·Optional diaphragm materials for wetted parts, explosion-proof housing structure;
·Industry-proven superiority and reliability.
Performance Parameters
Technical Performance
Applicable media: liquid, gas, or steam
Measurement range: Range 3 0-0.2~6.0kPa
Range 4 0-6.0~40.0kPa
Range 5 0-40.0~200kPa
Range 6 0-0.16~1.0MPa
Range 7 0-0.4~2.0MPa
Range 8 0-1.6~10MPa
Output signal: Linear output: 4~20mA output superimposed with HART protocol digital signal(two-wire system);
Square root output: when the input pressure is between 1.0%~100%, the output has a square root relationship with differential pressure; between 0%~0.1%, the output has a segmented linear relationship with differential pressure; there is no jump within 4~20mADC output, superimposed with HART? protocol digital signal(two-wire system), and users may select linear output or square root output according to field conditions.
Power Supply: externally supplied 24V DC, (power supply range 14.5V~45V)
Load characteristics: The maximum allowable load resistance in the load resistance circuit is Rmax=(E-10.5)/0.0236(Ω)
Installation in hazardous locations: flameproof type Exd Ⅱ CT6;
intrinsically safe type Exia Ⅱ CT6;
Load characteristics: After positive and negative shift, the upper and lower range limits shall not exceed the range limits. At the minimum range, the maximum positive shift is 0.975URL; the maximum negative shift is -URL. During square root output, positive and negative shift can be adjusted to calibrate 10% of the flow range.
Temperature range: Medium temperature -40~100℃
Storage temperature -40~100℃
Complete unit operating temperature -40~85℃
Relative humidity: 0~100%
Overpressure limit: Applying 0(absolute pressure)~13.76MPa pressure to either side of the transmitter will not damage the transmitter; the flange can withstand 68.9MPa pressure; normal operating pressure should be within 3.45kPa(absolute pressure) to the upper limit of the transmitter range.
Volume change: less than 0.16cm3
Damping: time constant adjustable between 0.2~32.0s.
Startup time: 3s, no preheating required.
Performance indicators:
(Under standard test conditions with no shift, 316 stainless steel isolation diaphragm, and other standard conditions.)
Turndown ratio: 40:1
Accuracy: Ranges 3, 4, 5
when the turndown ratio is 1:1 to 10:1, it is ±0.1% of the calibrated range,
when the turndown ratio is 10:1 to 40:1, it is ±0.05(1+0.1URL/range)% of range,
Ranges 6, 7, 8
when the turndown ratio is 1:1 to 10:1, it is ±0.15% of the calibrated range,
when the turndown ratio is 10:1 to 40:1, it is ±0.075(1+0.1URL/range)% of range,
Stability: six-month error is ±0.15% of the maximum range;
Temperature effect: Ranges 4, 5, 6, 7, 8
zero error is ±0.25% of the maximum range/55℃.
Total error including span and zero is ±0.5% of the maximum range/55℃.
Note: for Range 3, the temperature error should be doubled.
Overpressure effect: after applying pressure of 140kgf/cm2, the error is ±0.25% of the maximum range.
Static pressure effect: during linear output, zero error: after applying static pressure of 140kgf/cm2, the zero error of Ranges 4 and 5 is ±0.25% of the maximum range, and the zero error of Ranges 3, 6, 7, 8 is ±0.5% of the maximum range.
Range error: the error of Ranges 4, 5, 6, 7, 8 is -1±0.25%/6.89MPa of the maximum range, and the error of Range 3 is -1.5±0.25%. This is a system error and can be eliminated by calibrating according to the actual static pressure before installation.
Power supply effect: less than 0.005%/V of output range
Vibration effect: on any axis, at a frequency of 200Hz, the induced error is ±0.05%/g of the maximum range.
Load effect: as long as the voltage input to the transmitter is higher than 14.5V, there is no load effect within the load operating area.
Installation position effect: a zero position error not greater than 0.25 kPa may be generated at most, but it can be corrected and has no effect on the range;
Rotation of the measuring body relative to the flange has no effect.
Electromagnetic radiation: complies with IEC801 standard
Outline Structure
Structural materials:
Isolation diaphragm and vent/drain valve: 316 stainless steel, Hastelloy C, Monel;
Flange and connector: 316 stainless steel, Hastelloy C, Monel;
“O” ring(in contact with measuring medium): fluororubber, nitrile rubber, ethylene-propylene;
Filling fluid: silicone oil;
Bolts: carbon steel zinc-plated, 1Cr18Ni9, 0Cr17Ni4CuNb, 42CrMo;
Electrical housing: low-copper aluminum alloy;
Coating: epoxy resin;
Pressure connection fitting: for Ranges 3, 4, 5, the thread of the two-flange connection is 1/4-18NPT and the center hole spacing is 54mm;
Connector 1/2-14NPT or M20X1.5 male thread; when using a spherical cone sealing connector, the center spacing is 50.8, 54, 57.2mm;
Weight: 3.5kg(excluding options)
Since its establishment, Xi'an Shenghongchuang Instrument Co., Ltd. has mainly engaged in the R&D and production of pressure, level, temperature, differential pressure, digital display, weighing, and flow instruments. Main products include Swiss metallux ceramic piezoresistive sensors, self-developed ceramic capacitive pressure sensors, diffused silicon, ceramic piezoresistive, strain gauge, metal capacitive, ceramic capacitive pressure transmitters, remote pressure transmitters, high-temperature pressure transmitters, flush diaphragm pressure transmitters, anti-corrosion pressure transmitters, integrated/split level transmitters, anti-corrosion level transmitters, lightning-proof level transmitters, high-temperature guided-pressure level transmitters, straight rod level transmitters, flange level transmitters, air pressure transmitters, metal capacitive differential pressure transmitters, diffused silicon differential pressure transmitters, pressure controllers, thermocouple/RTD temperature transmitters, ultrasonic level meters
Notes 1.All supplied products are provided with product certificates and instructions, including product number, technical parameters, wiring, date of manufacture, etc. Please check carefully to avoid incorrect use.2.Wiring should be carried out strictly in accordance with our company instructions.3.This product is a precision instrument. Random disassembly, collision, dropping, or poking the sensor with sharp tools is prohibited.4.The transmitter can work immediately after power-on, but the output becomes stable after 30 minutes of preheating.5.If any abnormality is found during use, turn off the power, stop using it, inspect it, or contact our company's technical department directly.6.During transportation and storage, restore the original packaging and store it in a cool, dry, and ventilated warehouse.7.The quality warranty period is 12 months(damage caused by improper use such as pressure overload and wiring errors is not covered by the quality warranty).8.Special products are custom-made products, do not participate in the 7-day no-reason return policy, custom-made products have a lead time, and are non-returnable and non-exchangeable.