Common SP-111G pressure transmitter installation issues: a pitfall-avoidance guide for installing diffused silicon Housman sensors
Added to Favorites:125

Key Preparations Before Installing Diffused Silicon Hirschmann Pressure Sensors

Before installing pressure transmitters such as SP-111G and HBP-800D, technical evaluation personnel should focus on verifying three core parameters: media compatibility, pressure range, and environmental adaptability. Taking the PRC-905 pressure transmitter as an example, its diffused silicon sensor uses a 316L stainless steel isolation diaphragm, which can withstand strong acid and strong alkali media, but if the medium contains solid particles (such as slurry or fiber mixtures), a diaphragm protector must be installed or models with self-cleaning functions such as TPT-TPT503 should be selected.


According to the requirements of ISO 21873, the following preparations must be completed before installation:

  • Sealing surface treatment:Check the flatness of the flange sealing surface (Ra≤3.2μm), and the DN50 flange used with the SP-112G pressure transmitter must use a PTFE sealing gasket
  • Electrical parameter verification:Refer to the YM-1JY pressure transmitter specification sheet to confirm that the power supply voltage (10-30VDC) and output signal (4-20mA) match the control system
  • Mechanical stress relief:For models with remote transmission signals such as CPS-CPS2016, a stress-relief bend of ≥5cm must be reserved for cable laying

Media adaptation solutions for typical installation scenarios

Media TypeCompatible ModelsSpecial Configuration
High-temperature steam(≤200℃)PTG-PTG485Heat sink + ceramic diaphragm installed
High-viscosity oilVegabar-vegabar14Conical diaphragm design + pulse damper
Corrosive GasJN-8001Hastelloy C276 diaphragm

5 Technical Points for Electrical Connection and Signal Debugging

The installation of the electrical system of diffused silicon Hirschmann pressure sensors directly affects signal transmission stability. Engineering data from Xi'an Shenghongchuang Instrumentation shows that about 32% of field failures are caused by non-standard wiring operations. Taking the SP-111G pressure transmitter as an example, it uses a dedicated Hirschmann connector (protection rating IP67), and special attention should be paid to the following during wiring:


  1. Power isolation:An isolated safety barrier must be used to prevent signal drift caused by ground loop interference
  2. Cable selection:The CPS-CPS2016 model with remote transmission signal must use twisted shielded cable (AWG18-22)
  3. Anti-interference measures:The distance between the signal cable and the power cable must be ≥30cm, and when crossing, they should be arranged at a 90° right angle
  4. Alarm control setting:The relay alarm point of TPT-TPT503 must be set within 10%-90% of the measuring range
  5. Grounding specification:Comply with IEC 60364-5-54, and the system grounding resistance must be ≤4Ω

Troubleshooting common signal debugging issues

When the PRC-905 pressure transmitter shows abnormal signals, troubleshooting can be carried out according to the following process:
1. Use a multimeter to measure the supply terminal voltage (normal value 24VDC±10%)
2. Disconnect the load and check the no-load output current
3. Check whether the waterproof sealing ring of the Hirschmann connector is intact
4. Read the internal diagnostic code of the sensor through the HART protocol (for the code table, see Appendix B of the product manual)


Mechanical Installation and Maintenance Specifications

Correct mechanical installation can significantly extend the service life of diffused silicon sensors. According to GB/T 17614.3-2015, the installation of the SP-111G pressure transmitter must comply with the following guidelines:


  • Installation orientation:The angle between the centerline of the process connection axis and the direction of gravity must be ≤45° (to prevent media sedimentation)
  • Torque control:The installation torque for 1/2"NPT threads is 25-30N·m, and excessive tightening will cause diaphragm deformation
  • Vibration protection:In vibration-prone areas such as pump outlets, anti-vibration brackets should be installed or models with built-in dampers such as HBP-800D should be selected
  • Maintenance cycle:For TPT-TPT503 with alarm control, zero-point calibration is recommended every 6 months

Golden rules for maintenance

Special attention should be paid to the maintenance of the JN-8001 pressure transmitter:
• Use an alcohol cotton pad when cleaning the diaphragm (metal tools must not be used for scraping)
• Original factory parts must be used when replacing seals (for material codes, see the appendix of the dimensional drawing)
• During the warranty period, complete medium operating condition records must be provided for repairs (refer to the PRC-905 warranty terms)


Summary and Technical Service Support

Proper installation of diffused silicon Hirschmann pressure sensors is the prerequisite for ensuring the long-term stable operation of models such as SP-111G and Vegabar-vegabar14. As a high-tech enterprise, Xi'an Shenghongchuang Instrumentation provides the following professional support:


  • Free access to 3D installation dimension drawings for models such as YM-1JY and PTG-PTG485
  • A professional technical team provides on-site installation guidance (including debugging of CPS-CPS2016 with remote transmission signal)