When using the HP-HP1000 pressure transmitter,have you encountered inaccurate readings?As a professional product from Xi'an Shenghongchuang,correct installation is critical to measurement accuracy。This article analyzes the key installation points for diffused-silicon liquid and gas pressure sensors,helping you quickly troubleshoot common faults in models such as the MBS33 series and HP series,and ensuring accurate data acquisition at industrial sites。
When abnormal readings occur in the HP-HP1000 pressure transmitter,the installation process should be checked first。The core sensing element of a diffused-silicon sensor is extremely sensitive to mechanical stress,and excessive installation torque can cause zero drift of up to ±0.5%FS in models such as MBS33-060G3005。According to the requirements of the ISO 9001 quality management system,we recommend using a preset torque wrench and strictly controlling the flange installation torque within the range of 15-20N·m。At the same time,pipeline vibration is also a key factor affecting the accuracy of models such as M515N-00000E-018BG;when the vibration frequency exceeds 1kHz,an additional error of ±1.2% may occur。
The HP series pressure transmitters produced by Xi'an Shenghongchuang adopt third-generation diffused-silicon technology。The MBS33-060G3042 model provides temperature drift characteristics of ±0.25%FS within the range of -40~125℃。Special attention should be paid during installation:the impulse pipe length should not exceed 3 meters,and a slope of 1:10 must be maintained to prevent condensate accumulation。For T-T22 explosion-proof products,the flameproof surface treatment process must also comply with the requirements of the GB3836.1-2010 standard。The dedicated 2000L-L model mounting bracket we provide can effectively eliminate the impact of pipeline stress on K-A series sensors。
Under high-pressure operating conditions in the petrochemical industry,the diaphragm overload protection function of the HP-HP1000 is especially important。When the measured medium is corrosive gas,it is recommended to select the MBS33-060G3015 model with a Hastelloy diaphragm。A case study at a refinery shows that failure to use a pulse damper caused sampling value fluctuations of up to ±3% in the HP-2 model;after installing our patented buffer device,the fluctuation was reduced to ±0.3%。For the food and pharmaceutical industries,special attention should be paid to the CIP cleaning process of sanitary flanges to avoid disinfectant residues affecting the long-term stability of diffused-silicon elements。
According to the JJG 882-2019 verification regulation for pressure transmitters,we recommend on-site calibration of the MBS33 series every 12 months。When using standard instruments such as the FLUKE754,please note:1) the warm-up time should be no less than 30 minutes;2) the calibration points should include 10%,50%,and 90% of the measuring range。The HP-HP1000 intelligent diagnostic function provided by Xi'an Shenghongchuang can monitor sensor health status in real time through the HART protocol and provide early warnings of potential faults such as seal ring aging。For T-T22 models within the warranty period,we provide free on-site calibration service。
As a leading sensor manufacturer in Northwest China,we have a CNAS-certified testing laboratory and 20 years of accumulated expertise in diffused-silicon technology。All products such as MBS33-060G3007 have passed ROHS and CE certifications,and come with an extended 3-year warranty。For special operating conditions,dedicated models such as the 2000L-L high-temperature type(up to 150℃)can be custom-developed。Call 029-8456XXXX now to obtain the HP series installation guide,or schedule an on-site diagnostic service with an engineer to restore your pressure measurement system to optimal accuracy。