Pressure Transmitter Manufacturer
Consultation hotline:15529283736
News Center
—— NEWS CENTER ——
Xi'an Shenghongchuang Instrument Co., Ltd.
Contact: Mr. Zhang
Mobile: 15529283736
Email: shc-sensor@qq.com
Address: Fortune Building, Sanqiao Street, Xixian New Area, Xi'an, Shaanxi Province
This article provides a detailed analysis of the wiring diagram for the FPC-400-D-25-000 electronic pressure switch, including step-by-step high-definition illustrations for NPN/PNP relay signal alarm output. As a core product of Xi'an Shenghongchuang Instrumentation Co., Ltd., this digital intelligent pressure controller is widely used in the field of industrial flow control, helping technical personnel quickly master wiring specifications and ensure stable equipment operation.
The FPC-400-D-25-000 electronic pressure switch is an intelligent control device using a high-precision silicon piezoresistive sensor, and its core parameters include: 25MPa range, ±0.5%FS accuracy, and IP65 protection rating. This model supports NPN/PNP dual-mode relay output, features a built-in LED digital display for real-time pressure value display, and has upper/lower limit dual alarm functions. Compared with traditional mechanical pressure switches, its response speed is improved to ≤10ms, its mechanical life exceeds 100万 times, and it is especially suitable for industrial scenarios requiring fast response such as hydraulic systems and air compressors.
1.Power connection: connect the brown wire to DC24V+, and the blue wire to the negative terminal, using a shielded cable of 0.75mm² or above.2. Signal output: the black wire is the NPN collector open-circuit output, the white wire is the PNP output, and the load current is ≤100mA.3. Alarm setting: the alarm value can be set via the SET key on the panel, the green LED indicates normal working status, and the red LED is triggered for alarm. For the specific wiring method, refer to the figure below:
In the hydraulic system of an injection molding machine, the FPC-400-D-25-000 can precisely control the following by detecting changes in oil circuit pressure: 1) pressure holding during the injection stage; 2) low-pressure protection during mold opening; 3) system overload alarm. After adopting this device, a certain automotive parts manufacturer increased the qualified product rate by 12% and reduced fault downtime by 67%. Its IP65 protection design can adapt to the oily workshop environment, and the wide temperature range of -20~85℃ ensures normal use in northern winters.
Q1: No output signal from the relay? A: Check whether the power supply polarity is reversed, and measure whether the output voltage is ≥22V. If using NPN output, confirm that the load has been connected to the positive terminal.Q2: Display value drift? A: Perform zero-point calibration (press and hold the SET key for 5 seconds), and check whether there is pulsating pressure in the pipeline. It is recommended to carry out calibration every 6 months according to the GB/T15478-2015 standard.
As a national high-tech enterprise, we have: 1) independently developed MEMS sensor chip technology; 2) a CNAS-certified testing laboratory; 3) 72-hour rapid response service. Before leaving the factory, all pressure switches undergo: a) 5000 full-range fatigue tests; b) EMC anti-interference tests; c) high and low temperature cycle aging tests. If you need to obtain the complete technical manual for the FPC-400 series or customized solutions, please call 029-89300839 or visit the official website at www.shengchuang.com.
Related Recommendations