News Center

——  NEWS CENTER  ——

News Center
Contact Us

Xi'an Shenghongchuang Instrument Co., Ltd.

Contact: Mr. Zhang

Mobile: 15529283736
Email: shc-sensor@qq.com

Address: Fortune Building, Sanqiao Street, Xixian New Area, Xi'an, Shaanxi Province

DMP-DMP335 Pressure Transmitter User Guide: 5-Step Quick Installation Method for Diffused Silicon Haisman Sensor
Added to Favorites:125

Introduction

The DMP-DMP335 pressure transmitter, leveraging diffused silicon Hirschmann sensor core technology, is highly favored in the field of industrial flow control. This guide will detail a fast 5-step installation method to help you efficiently complete the deployment of FY-FY212, PMP131-A1B01A73, and other series products, ensuring the precise operation of DMK-DMK457 supporting equipment. As an expert in pressure measurement solutions, Xi'an Shenghongchuang Instrumentation analyzes the key technical performance points of the original genuine YM-110 for you.


In industrial automation control systems, the installation quality of pressure transmitters directly affects measurement accuracy and equipment service life. Especially for models using diffused silicon Hirschmann sensors, such as DMP-DMP335, their high-precision characteristics place higher requirements on installation procedures. This article will systematically introduce the preparation work before installation, specific operating steps, and subsequent verification methods, helping business evaluation personnel fully grasp the technical essentials.


Technical advantages of diffused silicon Hirschmann sensors

As the core component of pressure measurement, diffused silicon Hirschmann sensors are well known in the industry for their outstanding performance. Their technical features are mainly reflected in three aspects: first is media compatibility, with the sensor element using a 316L stainless steel diaphragm that can withstand corrosive media in industries such as petroleum and chemicals; second is temperature stability, where precision compensation technology keeps the output signal stable within the range of -20~+85℃; finally is long-term reliability, as tests show that the FY-FY212 pressure transmitter can achieve a service life of more than 8 years under typical working conditions.


Analysis of key performance indicators

Business evaluation should pay special attention to the following parameters:

  • Accuracy class: models such as FY-FY211 can reach 0.1%FS
  • Overload capacity: standard models can withstand 2 times full-scale pressure
  • Response time: real-time transmission of electrical signals, with a delay of less than 1ms
  • Interface standards: multiple thread specifications are available, such as M20×1.5 and G1/2

Detailed explanation of the five-step quick installation method

Step 1: Pre-installation inspection

Verify whether the model specifications of the DMP-DMP335 pressure transmitter are consistent with the design requirements, with重点 confirming the pressure interface type (threaded/flanged) and electrical connection method (Hirschmann connector/aviation plug). Check whether the operating voltage of the PMP131-A1B01A73 supporting instrument matches the 24VDC power supply requirement, and prepare the corresponding commissioning tools. For special media working conditions, it is recommended to choose corrosion-resistant models such as Domestic general-purpose pressure transmitter ZP-801 hydraulic oil pressure pneumatic sensor.


Step 2: Mechanical installation

Use a torque wrench to tighten the pressure interface according to the specified torque (usually 20-30N·m), avoiding excessive tightening that may cause diaphragm deformation. For vibration environments, it is recommended to install anti-vibration brackets. If special accessories such as 8472.25-5717 are used, ensure that the sealing gasket material is compatible with the measured medium. Pay attention to the flow direction marking during installation to prevent reverse installation from damaging the sensor.


Step 3: Electrical connection

Connect the power supply and signal wires according to the wiring diagram, paying special attention to the following:

  1. The polarity of the 24VDC power supply must not be reversed
  2. The shielded wire must be grounded at one end only
  3. Maintain a safe distance from the DMK-DMK457 supporting equipment

For explosion-proof locations, a junction box that meets the explosion-proof rating must be used.


Step 4: Parameter setting

Perform range calibration through the PMP131-A1B01A73 supporting instrument, and the setting methods include:

Parameter ItemSet valueRemarks
Measurement unitMPa/psi optionalAccording to process requirements
Output Signal4-20mA/0-10VMatch the control system
Damping time0.1-10s adjustableSuppress pipeline pulsation

Step 5: Functional verification

Use the stepped pressure test method to verify the linearity of models such as 30.600G-G, with the specific steps as follows:

  • Start from zero pressure and gradually load up to full scale
  • Record the output current value at each point
  • Perform a return-stroke test to check hysteresis error
  • Calculate the basic error, which should be ≤0.5%FS

Solutions to common problems

Signal abnormality troubleshooting

When the YM-110 pressure transmitter shows output fluctuations, it is recommended to check in the following order:

  1. Confirm that the supply voltage is stable at 24VDC±10%
  2. Test that the loop resistance does not exceed 500Ω
  3. Check whether the technical performance parameters of PTHY-A match the working conditions
  4. Eliminate sources of electromagnetic interference

Media compatibility issues

For special media (such as high-viscosity fluids), models such as 18.601G-G require attention to the following:


Summary and professional recommendations

Correct installation procedures can fully leverage the performance advantages of diffused silicon Hirschmann sensors. It is recommended that business evaluation personnel give priority to original genuine products such as the DMP-DMP335 pressure transmitter during equipment selection, and strictly follow the 5-step installation method in this article. As a leading provider of pressure measurement solutions in the industry, Xi'an Shenghongchuang Instrumentation can provide you with full-process technical support from selection consultation to installation and commissioning.


If you need to learn the detailed technical specifications of FY-FY212, DMK-DMK457, and other series products, or obtain the operating manual for the PMP131-A1B01A73 supporting instrument, please contact our technical consultant team immediately, and we will customize the optimal pressure measurement solution for you.

Submit